Specifications

Troubleshooting SiUS12-928_A
123 Service Diagnosis
5.16 Discharge Pipe Temperature Control
Remote
Controller
Display
F3
Outdoor Unit LED
Display
A 5 1 4 2 1 3 4 4 1
Method of
Malfunction
Detection
Detected by the discharge pipe thermistor
Malfunction
Decision
Conditions
If the temperature detected by the discharge pipe thermistor rises above , the compressor
stops.
The error is cleared when the discharge pipe temperature is dropped below .
If the error repeats 6 times, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Refrigerant shortage
Defective four-way valve
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective outdoor unit PCB
Water mixed in refrigerant
Defective electronic expansion valve
Defective stop valve
Troubleshooting
Check No.04
Refer to P.150
Check No.06
Refer to P.152
Check No.11
Refer to P.155
120°C (248°F)
107°C (225°F)
(R7141)
Caution
Malfunctioning
Discharge pipe thermistor
Outdoor heat exchanger thermistor
Outdoor temperature thermistor
Refrigerant shortage
Four way valve
Water mixed
Stop valve
Functioning
Functioning
Functioning
Malfunctioning
Malfunctioning
Check No. 06
Check the thermistors.
Check No. 11
Check the refrigerant
line.
Check No. 04
Check the electronic
expansion valve.
Replace the defective
thermistor.
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.