Specifications

Check SiUS12-928_A
151 Service Diagnosis
6.1.3 Four-Way Valve Performance Check
Check No.05
(R11717)
(R11725)
NO
YES
YES
NO
(Fig. 1)
Voltage at S80
208/230 VAC
ON
Compressor
Time
Turn off the power and turn it on
again.
Disconnect the connector for the
four way valve coil and check the
continuity.
Start heating operation.
Four way valve coil
Cooling / dry : No continuity
Heating : Continuity
Replace the outdoor unit
PCB.
Replace the four way valve
coil.
Replace the four way valve.
Four way
valve coil resistance at
1000 ~ 2000 Ω?
S80
voltage at 208/230
VAC with compressor
on? (Fig. 1)