Specifications

Field Settings SiUS12-928_A
223 Trial Operation and Field Settings
3.4 When 2 Units are Installed in 1 Room
When 2 indoor units are installed in 1 room, 1 of the 2 pairs of indoor unit and wireless remote
controller can be set for different addresses.
Both the indoor unit PCB and the wireless remote controller need alteration.
Indoor Unit PCB Cut the jumper JA on PCB.
Wireless remote
controller
Cut the jumper J4.
3.4.1 Jumper Settings
For the location of the jumper, refer to the page 18 and 20.
< Duct-Free System> < Slim Duct Built-in System >
1)Remove the front grille.
2)Remove the electrical box.
3)Remove the metal plate of the electrical
box.
Address
JA
Address
JA
EXIST
1
CUT 2
(R10274)
1 23
ADDRESS : JA
CUT
EXIST 1
2
ADDRESS
JA
JB
JC
(R10276)
(R4417)(R10275)
ADDRESS
J4
EXIST
CUT
1
2
J4
Address
J4
EXIST
1
CUT 2
J4
< Duct-Free System> < Duct Built-in System >
Jumper Function When connected
(factory set)
When cut
JB
(on indoor unit PCB)
Fan speed setting
when compressor
stops for thermostat
OFF. (Effective only
at cooling operation)
Fan speed setting ;
Remote controller
setting
Fan speed setting; “0” (The fan
stops.)
JC
(on indoor unit PCB)
Power failure
recovery function
Auto-restart The unit does not resume
operation after recovering from a
power failure. Timer settings are
cleared.