Specifications

Main Functions SiUS12-928_A
35 Function and Control
1.7 Thermostat Control
Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Thermostat OFF Condition
The temperature difference is in zone A.
Thermostat ON Condition
The temperature difference returns to zone C after being in zone A.
The system resumes from defrost control in any zone except A.
The operation turns on in any zone except A.
The monitoring time has passed while the temperature difference is in zone B.
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
Cooling / Dry
Duct-Free System
Slim Duct Built-in System
Heating
Duct-Free System
Slim Duct Built-in System
Refer to “Temperature Control” on page 29 for detail.
B
A
OFF
ON
C
Cooling : – 0.5˚C (– 0.9˚F)
Dry : – 0.5˚C (– 0.9˚F)
Room thermistor temperature – target temperature
– 1.5˚C (– 2.7˚F)
Cooling : – 2.0˚C (– 3.6˚F)
Dry : – 2.5 ~ – 2.0˚C (– 4.5 ~ – 3.6˚F)
(R12399)
B
A
OFF
ON
C
Cooling : –1.0˚C (–1.8˚F)
Dry : –1.0˚C (–1.8˚F)
Room thermistor temperature – target temperature
–1.5˚C (–2.7˚F)
Cooling : –2.0˚C (–3.6˚F)
Dry : –2.5 ~ –2.0˚C (–4.5 ~ –3.6˚F)
(R12400)
B
A
OFF
ON
C
1.5˚C (2.7˚F)
Room thermistor temperature – Target temperature
0˚C (0˚F)
(R12401)
1.0˚C (1.8˚F)
BB
AA
OFFOFF
ONON
CC
1.5˚C (2.7˚F)
0.5˚C (0.9˚F)
1.0˚C (1.8˚F)
Room thermistor temperature – target temperature
(R12402)