Specifications

SiUS12-928_A Control Specification
Function and Control 48
3.3.4 3-Minute Standby
Turning on the compressor is prohibited for 3 minutes after turning off.
(Except when defrosting.)
3.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows. (The
function is not used when defrosting.)
Value Unit
FCG 1 55
HzFCG 2 65
FCG 3 80
TCG 1 120
secondsTCG 2 200
TCG 3 470
FCG3
(Hz)
Frequency
(Sec.)
Time
FCG2
FCG1
TCG1 TCG2 TCG3
(R10540)