Precautions for New Refrigerant (R-410A) SiUS34-907
252 Precautions for New Refrigerant (R-410A)
Low pressure gauge
– 14.5 to 551 psi (– 76 cmHg to 38 kg/cm
2
)
1/4" 5/16" (2min 2.5min)
No oil is used in pressure test of gauges.
For prevention of contamination
Temperature scale indicates the relationship between pressure and temperature in gas saturated state.
Differences
Change in pressure
Change in service port diameter
7. Charge hose for R-410A
Specifications
Working pressure 737 psi (51.8 kg/cm
2
)
Rupture pressure 3684 psi (259 kg/cm
2
)
Available with and without hand-operate valve that prevents refrigerant from outflow.
Differences
Pressure proof hose
Change in service port diameter
Use of nylon coated material for HFC resistance
8. Charging cylinder
Specifications
Use weigher for refrigerant charge listed below to charge directly from refrigerant cylinder.
Differences
The cylinder can not be used for mixed refrigerant since mixing ratio is changed during charging.
When R-410A is charged in liquid state using charging cylinder, foaming phenomenon is generated inside
charging cylinder.
(Hose with ball valve)
Can not be used