Submittal
Daikin North America LLC 5151 San Felipe, Suite 500 Houston, TX 77056
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without
notice and without incurring any obligations)
Submittal Creation Date: July 2017 Page 1 of 4
Performance
Cooling (Btu/hr)
Rated (Min/Max)
15,000 (5,800 / 15,000)
Sensible @ AHRI
13,420
Moisture Removal gal/h
.8
Standard Operating Range
50°F – 115°F
Extended Operating Range*
0°F – 115°F
Rated Cooling Conditions:
Indoor: 80°F DB/67°F WB
Outdoor: 95°F DB/75°F WB
*With field settings and wind baffle
Heating (Btu/hr)
1:@ 47° Rated (Min/Max)
18,000 (5,800 / 18,000)
2: @ 17° Rated
11,900
3: @ 5° Max
8,050
Operating Range
5°F – 65°F
1: Rated Heating Conditions:
Indoor: 70°F DB/60°F WB
Outdoor: 47°F DB/43°F WB
2: Rated Heating Conditions:
Indoor: 70°F DB/60°F WB
Outdoor: 17°F DB/15°F WB
3: Rated Heating Conditions:
Indoor: 70°F DB/60°F WB
Outdoor: 5°F DB/5°F WB
Submittal Data Sheet
FTXS15LVJU / RXS15LVJU
1.25-Ton Wall Mounted Heat Pump System
Efficiency
Cooling
Heating
SEER
20.6
HSPF
11.6
EER
14.4
COP
4.00
Electrical
208/60/1
230/60/1
System MCA
13.75
13.75
System MFA
20
20
Compressor RLA
4.7
4.2
Outdoor fan motor FLA
.32
.32
Outdoor fan motor W
53
53
Indoor fan motor FLA
.31
.31
Indoor fan motor W
48
48
MFA: Max. fuse amps MCA: Min. circuit amps (A) FLA: Full load amps (A)
RLA: Rated load amps (A) W: Fan motor rated output (W)
Piping
Liquid (in)
1/4
Gas (in)
1/2
Drain (in)
5/8
Max. Interunit Piping Length (ft)
98.4
Max. Interunit Height Difference (ft)
65.6
Chargeless (ft)
32.8
Additional Charge of Refrigerant (oz/ft)
.21
Indoor Specifications
Airflow Rate (cfm)
Cooling
Heating
H
M
H
M
568
477
593
505
L
SL
L
SL
385
360
417
371
Sound (dBA)
H / M / L / SL
45 / 40 / 35 / 32
43 / 38 / 33 / 30
Dimensions (H × W × D) (in)
13-3/8 × 41-5/16 × 9-3/4
Weight (Lbs)
31
Outdoor Specifications
Compressor
Hermetically Sealed Swing Type
Refrigerant
R-410A
Refrigerant Oil
PVE (FVC50K)
Airflow Rate (cfm)
Cooling
Heating
H
1,713
H
1,405
L
1,469
L
1,306
Sound Power Level (dBA)
61 / 62
Dimensions (H × W × D) (in)
28-15/16 × 32-1/2 × 11-13/16
Weight (Lbs)
104
Job Name:
Tag#
Complete warranty details available from your local dealer or at
www.daikincomfort.com. To receive the 12-Year Parts Limited
Warranty, online registration must be completed within 60 days of
installation. Online registration is not required in California or Quebec.
If product is installed in a commercial application, limited warranty
period is 5 years.