Product Overview
Data sheet ESBE Series 30 MR
Thermostatic Mixing Valves
VDKIE122 © Danfoss 05/08
0.5 US gpm whenever the mixed water
temperature exceeds the setting by 18°F
(10°C) due to cold-water supply failure. If the
outlet temperature exceeds the setting by
36°F (20°C) the hot water supply port will
close.
The angle flow pattern of the Series 30 MR
makes installation simple, requiring a minimum
number of fittings for connecting the three
ports.
Available connections:
•
Threaded body (FPT)
Solder (Union connection)
Solder c/w 2 check valves (Union connection)
CPVC (Union connection)
Compression (3/4” only)
Maximum working pressure:•
150 psi (10 bar)**.
**Max. working pressure for CPVC: 80 psi (5.5 bar)
Maximum system differential pressure•
between hot and cold: 44 psi (3 bar).
Maximum system differential pressure:•
72 psi (5 bar).
Maximum hot water inlet temperature:•
194°F (90°C).
Minimum required flow***: 0.5 USgpm•
***For correct temperature control
Applications/
Features:
Specifications:
1
The Series 30 MR valves are compact
thermostatic mixing valves that have been
designed for hot water heating systems and
domestic hot water distribution systems for
multiple fixtures.
The Series 30 MR offers a choice of four
temperature ranges and a wide selection of
connection types.
Series 30 MR valves provide an anti-scald
function that will reduce the hot water flow to
ASSE-1017 listed*
•
Anti-scald function (see above).•
Designed for mixing purposes.•
Long life and easy maintenance.•
Quiet operation.•
Compact design and lightweight.•
Snap-on cover for dirt protection and to•
prevent unauthorized adjustment or
tampering.
Cover label for recording setting•
information including recorded outlet
temperature and date installed.
Available temperature ranges:•
70°F – 110°F (20°C – 45°C)
85°F – 120°F (29°C – 49°C)*
95°F – 140°F (35°C – 60°C)*
85°F - 160°F (30°C - 70°C) (3/4” only)
*Only ranges 85°-120°F and 95°-140°F are listed to
ASSE-1017 standard.
ASSE 1017
Listed For
Hot Water
Distribution
Systems*