Submittal Sheet

Data sheet Temperature sensors type NTC for ETC / ERC controllers
Danfoss A/S (ADAP-KOOL®), 2016-07 DKRCC.PD.S00.A4.02 / 520H5357 3
PVC Standard sensors
Double insulated
Operating temperature range -40 to 80°C
Thermistor Encapsulated in plastic housing
Connecting cable PVC double insulated
Climatic category (IEC 60068-1) 40/80/56
Rated resistance at 0°C 16330 Ω ±2% (±0.4°C)
Rated resistance at 25°C 5000 Ω
Insulation resistance >1000 MΩ
Voltage proof 3750 V
Thermal time constant Approx. 35 sec.
Typical applications Air sensing, evaporator sensing, condenser sensing
TPE precision sensors
Double insulated
Operating temperature range -20 to 100°C
Thermistor Encapsulated in plastic housing
Connecting cable Thermoplastic elastomer double insulated
Climatic category (IEC 60068-1) 40/80/56
Rated resistance at 0°C
16330 Ω ±1% (±0.2°C)
Rated resistance at 25°C 5000 Ω
Insulation resistance >100 MΩ
Voltage proof 3750 V
Thermal time constant Approx. 8 sec.
Typical application Ice bank
Technical data
TPFE low temperature sensors
Basic insulated
Operating temperature range -65 to 200°C
Thermistor Encapsulated in plastic housing
Connecting cable Teflon single insulated
Climatic category (IEC 60068-1) 40/80/56
Rated resistance at 0° C
6 k±1% (±0.2° C)
Insulation resistance
>100 M
Voltage proof 1250 V
Thermal time constant Approx. 7 sec.
Typical application Low temperature freezers
NTC sensor for heating application
FEP insulation
Operating temperature range -40 to 200°C
Thermistor Encapsulated in stainless steel housing. AISI 305
Connecting cable Silicone rubber cable
Degree of protection IP67
Rated resistance at 0°C 346,9 kOhm (tolerance at 0°C ±2.2%)
Rated resistance at 25°C 100,0 kOhm (tolerance at 25°C ±1.0%)
Insulation resistance >100 MΩ
Voltage proof 3750 V
Thermal time constant Approx. 8 sec.
Typical application Heating application