User`s guide
Installation
Connecting the temperature sensors and the bus
Terminal Description Type (recomm.)
15 and 16 System device bus*, 
connections for room 
panel** / remote control** / 
(relay module)
ECA 60 / 62
ECA 61 / 63
17 and 16 S1 Outdoor temperature
sensor 
ESMT
18 and 16 S2 Flow temperature sensor, 
circuit I
(and charging temperature 
sensor, DHW circuit)
ESM-11 / ESMC / 
ESMU
19 and 16 S3 Return temperature sensor ESM-11 / ESMC / 
ESMU
20 and 16 S4 Flow temperature sensor, 
circuit II
ESM-11 / ESMC / 
ESMU
21 and 16 S5 Return temperature sensor, 
circuit II 
or charging temperature 
sensor, DHW circuit
or lower tank temperature 
sensor
ESM-11 / ESMC / 
ESMU
ESMU / ESMB
22 and 16 S6 Upper tank temperature 
sensor
ESMU / ESMB
*  The system device bus / room panel / remote control is only active
  when the outdoor temperature sensor is connected.
**  Either room temperature sensor or room panel / remote control
Establish the jumper from 16 to common terminal.
Wire cross section for sensor connections: 
  Min. 0.4 mm
2
Total cable length:   Max. 125 m (all sensors incl. system device 
bus)
Cable lengths of more than 125 m may cause noise sensibility 
(EMC).
Connecting and placing the 
temperature sensors
14a