Service parameter(s) 141
141 Override input selection
Circuit Setting range Factory setting
(I) / (II) OFF / 1 ... 6 (OFF) / (OFF)
Choose an unused temperature sensor input for overriding the 
schedule for circuit I and / or circuit II.
The override can be activated for comfort or setback mode.
For override the controller's mode must be in 'scheduled 
operation'!
OFF:  The controller's schedule is not overridden.
1 ... 6:  Select an unused sensor input S1 ... S6 for 
the override of the circuit in question.
Connection example
If the override switch has gold-plated contacts, you can 
choose one of the following solutions:
Closed switch:
Comfort temperature 
Closed switch:
Setback temperature
Changeover switch:
Setback or comfort temperature
Connection example with ECA 9010
(used if the override switch does not have gold-plated 
contacts).
16 - Brown 
15 - Red 
Green (S1 ... S6)
The ECA 9010 module is powered by the system device bus, which 
means that the bus must be active. The bus is activated by setting 
the controller address to 15 (line 199). 