Installation guide

35
VMBME102
Sub menu INFORMATION -> TEMPERATURE
Used to indicate the prevailing temperatures, history and set/calculated values. History can be accessed to view all the values by pressing
the right arrow to present a graph of the last 100 measurement points for the set time interval (SERVICE -> INSTALLATION -> LOGTIME). In
the event of an alarm, history stops being logged until the alarm is reset by changing the operating mode to OFF.
Menu selection Meaning Factory setting
OUTDOOR Shows the actual outdoor temperature. -
ROOM Shows the actual set temperature. -
SUPPLY PIPE Shows the actual supply temperature. The calculated supply temperature to the
heating system group is within brackets.
During hot water production in operating mode ADD.HEAT the value for HOT
WATER STOPP + 5° is shown within brackets.
-
RETURN PIPE Shows the actual return temperature. The stop temperature, MAX RETURN is
within brackets.
-
HOT WATER Shows the actual hot water temperature. -
INTEGRAL Shows the actual calculated value for integral. -
BRINE OUT Shows the actual temperature for the brine systems supply pipe. -
BRINE IN Shows the actual temperature for the brine systems return pipe. -
POOL
(Expansion card)
Only appears if POOL is selected. Shows the actual pool temperature. The set
pool temperature is shown in brackets.
-
SHUNTGROUP
(Expansion card)
Only appears if SHUNTGROUP is selected. Shows the actual supply temperature.
The calculated supply temperature to the shunt group is within brackets.
-
COOLING
(Expansion card)
Only appears if COOLING is selected. Shows the actual supply temperature. The
set point value is shown in brackets.
-
CURRENT
(Expansion card)
Only appears if CURRENT LIMITER is selected. Shows the actual current con-
sumption. The set value for MAX CURRENT is shown between brackets.
-
Sub menu INFORMATION -> OPERAT. TIME
Used to show the operating time for each component. Time given in hours.
Menu selection Meaning Factory setting
HEATPUMP Compressor operating time for both heating and hot water production. -
ADD. HEAT 1 Operating time auxiliary heater power stage 1 with full output 3 kW (VL). -
ADD. HEAT 2 Operating time auxiliary heater power stage 2 with full output 6 kW (VL). -
ADD. HEAT 3 Operating time auxiliary heater power stage 3 with full output 6 kW (VL). -
HOT WATER Operating time hot water with compressor. -
COOLING
(Expansion card)
Operating time passive cooling. -
COOLING ACTIVE
(Expansion card)
Operating time active cooling. -
Sub menu INFORMATION -> DEFROST
Used to obtain information about outdoor unit defrosting and to make certain settings.
Menu selection Meaning Factory setting
DEFROSTS Total number of defrosts carried out. -
BETW. 2 DEFR The operating time of the compressor in minutes between the 2 last defrosts. -
TIME SINCE DEFROST The operating time of the compressor in minutes since last defrost. -
FAN H OFF AT Fan high speed is deactivated at this temperature and low speed is activated. 12°C
(interval: 10°C / 20°C)
DEFROST CURVE Here, the angle of the defrost curve can be changed using the right-hand arrow
and by either pressing + or – (Change the start temperature for defrost).
-10°C
(interval: -13°C / -7°C)
MANUEL DEFR By using the right-hand arrow + or -, defrost can be started manually (shunts
+20°C for 10 minutes).
0 (interval: 0 / 1)