Installation guide

InstallationGuideECLComfort210/310,applicationA231/A331
Inputtype
11327
CircuitSettingrange
Factorysetting
1
OFF/AI/DIOFF
Choiceofpressureinputsignal.
OFF:


AI:

DI:

 
Time-out
11323
CircuitSettingrange
Factorysetting
1
0...1000s20s
Settingofthemax.timeforrell.Thepressure,measuredbyS10,mustbe
OKwithinthesettime.Ifnot,therellwaterfunctionstopsandanalarm
isactivated.
PressureOK
NotOK
Rell
ON
OFF
Seconds
(s)
Time-out
PressureOK
NotOK
Rell
ON
OFF
Alarm
ON
OFF
Seconds
(s)
Time-out
Pressure,des.(desiredpressure)
11321
CircuitSettingrange
Factorysetting
1
0.0...25.0bar3.0bar
Settingofthedesiredstaticpressureontheradiator(consumer)side.See
also'Pressurediff. '
Pressure(bar)
Pressuredifference
Pressure
Desired
pressure
RellON
OFF
Time



