Installation guide

InstallationGuideECLComfort210/310,applicationA231/A331
Pressure,diff.(switchingdifference)
11322
CircuitSettingrange
Factorysetting
1
0.1...5.0bar1.5bar
Settingoftheswitchingdifferenceformeasuredstaticpressure(pressure
transmitter).Thedifferenceissymmetricalaroundthe'Pressuredes.'See
also'Pressuredes. '


Pexercise(pumpexercise)
11320
CircuitSettingrange
Factorysetting
1
OFF/1...200sOFF
Thetimethepumpisactivatedduringexercise.Exercisetakesplaceevery
day(at12:00).
OFF:

1...200:

Valvedelay
11325
CircuitSettingrange
Factorysetting
1
0...30s
1s
SettingofthetimeforactivationoftheON/OFFvalveafterstartoftherell
waterpump.
RellpumpON
OFF
Rellvalve
ON
OFF
Time
Valvedelay’
No.ofpumps
11326
CircuitSettingrange
Factorysetting
1
OFF/1...2
1
Settingofthenumberofpumpsintherellwatercircuit.
OFF:


1...2:

ECL485
communication
bus
Rellwater
pump
Rellwater
valve










