Operating instructions
8-05 End-of-Timeout Function
Option: Function:
Select the action after receiving a valid control word following a time-out. This parameter is active
only when par.8-04 
Control Timeout Function
 is set to [Set-up 1-4].
[0] Hold set-up Retains the set-up selected in par.8-04 
Control Timeout Function
 and displays a warning, until par.
8-06 
Reset Control Timeout
 toggles. Then the frequency converter resumes its original set-up.
[1] * Resume set-up Resumes the set-up active prior to the time-out.
8-06 Reset Control Timeout
Option: Function:
This parameter is active only when the choice 
Hold set-up
 [0] has been selected in par.8-05 
End-
of-Timeout Function
 .
[0] * Do not reset Retains the set-up specified in par.8-04 
Control Timeout Function
, [Select setup 1-4] following a
control time-out.
[1] Do reset Returns the frequency converter to the original set-up following a control word time-out. When the
value is set to 
Do reset
 [1], the frequency converter performs the reset and then immediately reverts
to the 
Do not reset
 [0] setting.
8-07 Diagnosis Trigger
Option: Function:
This parameter has no function for LonWorks.
[0] * Disable
[1] Trigger on alarms
[2] Trigger alarm/warn.
8-10 Control Profile
Option: Function:
Select the interpretation of the control and status words corresponding to the installed fieldbus.
Only the selections valid for the fieldbus installed in slot A will be visible in the LCP display.
[0] * FC profile
8-50 Coasting Select
Option: Function:
Select control of the coasting function via the terminals (digital input) and/or via the bus.
[0] Digital input
[1] Bus Activates Start command via the serial communication port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs.
NB!
This parameter is active only when par.8-01 
Control Site
 is set to [0] 
Digital and control word
.
8-51 Quick Stop Select
Select control of the Quick Stop function via the terminals (digital input) and/or via the bus.
Option: Function:
[0] Digital Input
VLT® FC 100 LonWorks 8 Parameters
MG.11.E2.02 - VLT
®
 is a registered Danfoss trademark
51