Specifications
2.6.6 Closed Loop Set-up Wizard
The closed loop setup wizard can be found in the quick menu.
6-29 Terminal 54 Mode
[1] 
 Voltage mode 
6-25 Terminal 54 High Ref./Feedb. Value
0050
 Hz
20-94 PI Integral Time
9999
 s
Current
Voltage
This dialog is forced to be set to 
[2] Analog in 54
24
25
26
27
28
29
30
31
20-00 Feedback1 source
[2]
 Analog in 54
3-10 Preset reference [0]
[1] 
 0
3-03 Max Reference
[1]
 50
3-02 Min Reference
[1]
 0
Asynchronous Motor
1-73 Flying Start 
[0]
 No
1-22 Motor Voltage
0050
 V
1-24 Motor current
04.66
 A
1-25 Motor nominal speed
1420 
 RPM
3-41 Ramp 1 ramp-up time
0003
 s
3-42 Ramp1 ramp-down time
0003
 s
3
4
5
6
7
13
14
15
17
18
18a
20
21
22
23
32
33
34
35
 36
37
0-03 Regional Settings
[0]
 International
4-12 Motor speed low limit
0016 
 Hz
4-14 Motor speed high limit
0050
 Hz
1
130BB631.11
1-20 Motor Power
1.10 
 kW
1-23 Motor frequency
0050 
 Hz
6-22 Terminal 54 Low Current
 4 mA
6-24 Terminal 54 Low Ref./Feedb. Value
0016
 Hz
6-23 Terminal 54 High Current
20
 mA
6-25 Terminal 54 High Ref./Feedb. Value
50
0,01
s
20-81 PI Normal/Inverse Control
[0]
 Normal
20-83 PI Start Speed
0
 Hz
20-93 PI Proportional Gain
0,01
 s
1-29 Automatic Motor Adaption
[1] 
 Enable
6-20 Terminal 54 Low Voltage
0,07
 V
6-24 Terminal 54 Low Ref./Feedb. Value
0
 Hz
6-21 Terminal 54 High Voltage
10
 V
6-26
Terminal 54 Filter time constant
3-10 Preset reference is the set-point
Please note that Terminal 27 Digital Input (par. 5-12) 
has coast inverse as default setting. This means that 
AMA can not be performed if there is no 24V to terminal
27 so please connect terminal 12 to terminal 27.
0-01 Configuration Mode
[0]
 Open Loop
2
Introduction to VLT HVAC Ba... VLT HVAC Basic Drive Design Guide
28 MG.18.C2.02 - VLT
®
 is a registered Danfoss trademark
22