Installation guide
10.4 Filling and bleeding the brine system
10.4.1 Introduction
Before filling the brine system, the electrical installation must be completed so that it is possible to operate
the brine pump.
Before filling the brine system for DHP-A Opti the water heater MUST be filled.
Always check local rules and regulations before using anti-freeze.
For DHP-C Opti W/W: The pressure on the brine system must not exceed 3 bar and the difference pressure
must be at least 120 kPa.
Bleed the system thoroughly
N
Anti-freeze with corrosion protection additives must be used and mixed to achieve frost protection down to
-17 ±2°C for DHP-H, DHP-L and DHP-C Opti.
N
Use only of Danfoss recommended ethylene glycol as anti freeze for DHP-A mixed to achieve frost protection
down to -32±1°C.
VMGFQ202 Danfoss Heating Solutions
62
Installation Guide Domestic heat pumps