Installation guide

10.4.2 Calculate volume
For DHP-H, DHP-L and DHP-C the volume of the brine system is calculated as follows:
Heat pump (exchanger and piping) approximately 2 litres
Bleed and expansion tank approximately 3 litres
Collector (single pipe):
PEM 40 approximately 1.0 litre/m
PEM 32 approximately 0.6 litre/m
Cu 28 approximately 0.5 litre/m
10.4.3 Calculate volume for brine between the indoor and outdoor unit
For DHP-A Opti the volume of the brine system is calculated as follows:
Heat pump (exchanger, pipe and outer jacket) approximately 47 litres
Expansion vessel approximately 3 litres
Outdoor unit approximately 7 litres
Collector (single pipe): 28 mm pipe approximately 0.5 litre/m
40 mm PEL hose (between heat pump an outdoor unit) approximately 1 litre/m
10.4.4 Filling device
When the filling device is installed on the return pipe, remember to turn the strainer cover upwards in order to minimise the amount of
air that gets into the brine system when cleaning the filter.
A
B
C
A Shut-off valve
B Shut-off valve
C Dirt strainer with shut off valve
Danfoss Heating Solutions VMGFQ202
63
Installation Guide Domestic heat pumps