Installation Guide
Schrader valve Installation
Danfoss
23Z12.13
1 Nm (5 in.-lbs)
≤ 50 °C (250 °F)
Initial pressure drop:
Record initial pressure drop and check again after 72 hours of operation. Replace drier if the pressure
drop ([bar] / [psi]) across the core exceeds the following values.
Refrigerant
Evaporator temperature
-40 °C / -40 °F -28.9 °C / -20 °F -17.8 °C / 0 °F -6.7 °C / 20 °F 4.4 °C / 40 °F
[bar] [psi] [bar] [psi] [bar] [psi] [bar] [psi] [bar] [psi]
R404A, R407C, R507, R22
0.04 0.50 0.07 1.00 0.10 1.50 0.15 2.00 0.20 3.00
R134a
– – 0.04 0.50 0.07 1.00 0.10 1.50 0.15 2.00
R410A
0.07 1.00 0.10 1.50 0.15 2.00 0.20 3.00 0.07 1.00