Schrader valve Installation
Danfoss
23Z12.13
1 Nm (5 in.-lbs)
≤ 50 °C (250 °F)
Initial pressure drop:
Record initial pressure drop and check again after 72 hours of operation. Replace drier if the pressure
drop ([bar] / [psi]) across the core exceeds the following values.
Refrigerant
Evaporator temperature
-40 °C / -40 °F -28.9 °C / -20 °F -17.8 °C / 0 °F -6.7 °C / 20 °F 4.4 °C / 40 °F
[bar] [psi] [bar] [psi] [bar] [psi] [bar] [psi] [bar] [psi]
R404A, R407C, R507, R22
0.04 0.50 0.07 1.00 0.10 1.50 0.15 2.00 0.20 3.00
R134a
0.04 0.50 0.07 1.00 0.10 1.50 0.15 2.00
R410A
0.07 1.00 0.10 1.50 0.15 2.00 0.20 3.00 0.07 1.00