Installation manual

Connecting the inverters
Samil Power
Solar-Log
1000/500/200
Installation 119 of 268
2. Connect terminals 6,7 and 8 on inverter 1 to terminals 3,4 and 5 on
inverter 2.
3. Connect the other inverters to each other in the same way.
4. Terminate on the last inverter:
Bridge between pins 9 and 10.
5. Close inverters.
6. Insert the terminal block connector into the SolarLog™ RS485 socket.
Inverter settings
The following values must be set in the inverter setup:
COM_485 to 19200bps
COM_Pari to Even
COM_Stop to 2bit
Please follow the instructions in the manufacturer's handbook for this.
Allocate communication address
Recommendation: Continuous numbering starting with 1.
Setting: Using the inverter operating display
Procedure: As set out in the inverter's instructions
4.58 Samil Power
Overview
Interface integrated
2 RJ11 sockets inside the inverter.
4 pin wiring
Communication address does not have to be allocated.
Work steps
Switch off the inverters and the SolarLog™; (Page 16).
Connect inverters to the Solar Log
Connect the inverters to each other
Connecting inverters to the Solar-Log™
The wiring is done using the
ready-made data cable (optional extra; not supplied)
self-made, shielded 4 wire data cable and terminal block connector
(Page 15).