Technical data

The selection of the mains circuit breaker rating depends on the wiring design (wire cross- sec-
tional area), cable type, wiring method, ambient temperature, inverter current rating etc. Derat-
ing of the circuit breaker rating may be necessary due to self-heating or if exposed to heat. The
maximum output current per phase can be found in the table.
TripleLynx CN
8 kW
TripleLynx CN
10 kW
TripleLynx CN
12.5 kW
TripleLynx CN
15 kW
Maximum inverter current 12 A 15 A 19 A 22 A
Recommended fuse type gL/gG 16 A 16 A 20 A 25 A
Table 5.2: Mains Circuit Specifications
Cable Condition Specification
AC 5 wire cable Copper
Outer diameter 18-25 mm
Insulation strip All 5 wires 16 mm
Max. recommended cable length
TripleLynx CN
8 kW and 10 kW
2.5 mm
2
21 m
4 mm
2
34 m
6 mm
2
52 m
10 mm
2
87 m
Max. recommended cable length
TripleLynx CN
12.5 kW
4 mm
2
28 m
6 mm
2
41 m
10 mm
2
69 m
Max. recommended cable length
TripleLynx CN
15 kW
6 mm
2
34 m
10 mm
2
59 m
PE Cable diameter at least as phase cables
DC Max. 1000 V, 12 A
Cable length
4 mm
2
- 4.8 Ω /km
< 200 m*
Cable length
6 mm
2
- 3.4 Ω /km
>200-300 m*
Mating connector Multi-contact PV-ADSP4./PV-ADBP4.
* The distance between inverter and PV array and back, plus the summarised length of the cables used for
PV array installation.
Table 5.3: Cable Requirements
Note:
Avoid power loss in cables of more than 1 % of nominal inverter rating.
Illustration 5.1: TripleLynx CN 8 kW Cable Losses [%] versus Cable Length [m]