User manual

[Setup Grid management]
Set up ancillary services such as Power Level Adjustment (PLA) and Reactive Power in this area.
6.6.1.
General
[1] [Plant]
Illustration 6.14: General
Item Description
Nominal plant AC power Enter the total nominal AC power for the entire plant. This value is necessary for
correct calculation of the absolute reactive power Q.
Q and PF settle time Enter the system settling time for reactive power regulation.
Range: 10 – 60 seconds.
Control type Specifies whether the control should be Open loop (enabled) or Off (disabled).
Reference value Select a reference for reactive power
Grid management box
Reactive power Q
Power factor PF
Set point curve PF(P)
Set point curve Q(U)
Grid management box
The grid management box receives set point values for reactive power and PLA from
the DNO. Configure the grid management box inputs under: Relay configuration. For
more information refer to the TripleLynx CN Reference Manual and the Grid Manage-
ment Box Manual.
Reactive power Q
Enter the fixed set point value for the plant reactive power Q as either:
- percentage value of the nominal plant AC power (%)
Range: 0 60% of the nominal plant AC power, over-excited or under-exci-
ted.
- value of Q (kVAr)
Power Factor PF
Enter the fixed set point value for the plant power factor.
Range: 1 – 0.8 over-excited or under-excited.
Set point curve PF(P)
The power factor is defined as a function of the plant output power. Enter the values for the set
point curve under:
PF(P) Curve
.