2.2 Cabling of the Networks
2.2.1 BACnet MS/TP Cabling (NW #2)
To ensure correct functionality of the BACnet MS/TP
network, be sure to do the cabling correctly. Pay special
attention to mounting of the cable shield and to
termination of the network.
NOTICE
Never connect the shield to terminal 61 on the
frequency converter.
UBR-01
D
FC 102
E
B+ A- Shld
61 68 69
130BF304.11
30 A-
B+
Vacon 100
F
Illustration 2.2 Grounding Shielded Cables
Shielding of frequency converters connected to the same
ground potential
1. Use an adequate equalizing cable to eliminate
the risk of equalizing current running into the
shield of the BACnet cables.
2. Mount the shield at the terminal marked Shld on
the router.
3. On the frequency converters, connect the shield
to the ground shield brackets.
Shielding of frequency converters without the same
ground potential
If the frequency converters do not have the same ground
potential, only connect the shield to ground in 1 location.
Expect a lower EMC performance.
2.2.2 Ethernet Cabling (NW #1)
NOTICE
EMC INTERFERENCE
Use shielded cables for motor and control wiring, and
separate cables for eldbus communication, motor
wiring, and brake resistor. Failure to isolate eldbus
communication, motor, and brake resistor cables can
result in unintended behavior or reduced performance.
Minimum 200 mm (7.9 in) clearance between power,
motor, and control cables is required. For power sizes
above 315 kW (450 hp), increase the minimum distance
to 500 mm (20 in).
NOTICE
When the eldbus cable crosses a motor cable or a brake
resistor cable, ensure that the cables cross at an angle of
90°.
130BD866.12
≥200 mm (7.9 in) or
≥500 mm (20 in)
2
1
1 Ethernet cable
2
90° crossing
Illustration 2.3 Cable Routing
For the Ethernet, use standard shielded Cat5e patch cables.
Maximum cable length is 100 m (328 ft).
An Ethernet switch distributes the packets to the partic-
ipants on the Ethernet network. For industrial installation,
only use industrial graded products as other products may
cause faults and sporadic loss of communication.