Technical data

VLT
®
2800 Series
229 Frequence bypass, bandwidth
(FREQ BYPASS B.W.)
Value:
0 (OFF) - 100 Hz
0Hz
Function:
Some systems call for some output frequencies
to be avoided because of mechanical resonance
problems in the system. In parameters 230-231
Freque ncy bypass these output frequencies can be
programmed. In this parameter a bandwidth can be
defined on either side of these frequencies.
Description of choice:
The frequency set in this parameter will be centered
around parameters 230 Frequency bypass 1
and 231 Frequency b ypa ss 2.
230 Frequency bypass 1 (FREQ. BYPASS 1)
231 Frequency bypass 2 (FREQ. BYPASS 2)
Value:
0 - 1000 Hz
0.0 Hz
Function:
Some systems call for some output frequencies
to be avoided because of mechanical resonance
problems in the system.
Description of choice:
Enter the frequencies to be avoided. See also
parameter 229 Frequency bypass, bandwidth.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.A9.02 - VLT is a registered Danfoss trademark
34