Technical data
VLT
®
6000 HVAC
■ Installation of VLT 6400-6550 380-460 V Compact
IP 00, IP 20 and IP 54
Cooling Side-by-side
All units in the above-mentioned series require a
minimum space of 400 mm above the enclosure
and must be installed on a plane floor. This applies
to both IP 00, IP 20 and IP 54 units.
Gaining access to VLT 6400-6550 requires a
minimum space of 605 mm in front of the frequency
converter.
All IP 00, IP 20 and IP 54 units in the
above-mentioned series can be installed side by side
without any space between them, since these units
do not require cooling on the sides.
■ IP 00 VLT 6400-6550 380-460 V
The IP 00 unit is designed for installation in a cabinet
when installed according to the instructions in the
VLT 6400-6550 Installation Guide MG.56.AX.YY.
Please note, that the same conditions as for NEMA
1/ IP20 and IP54 must be fulfilled.
MG.60.C8.02 - VLT is a registered Danfoss trademark