Specifications

5.2.3 Fuses and Circuit Breakers
Branch circuit protection
To protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc.,
must be short-circuit and overcurrent protected according to national and local regulations.
Short circuit protection
Danfoss recommends using the fuses and circuit breakers listed in Table 5.15 to protect service personnel or other
equipment in case of an internal failure in the unit or short-circuit on DC-link. The frequency converter provides full short
circuit protection in case of a short-circuit on the motor.
Overcurrent protection
Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection must always be
carried out according to local and national regulations. Circuit breakers and fuses must be designed for protection in a
circuit capable of supplying a maximum of 100,000 A
rms
(symmetrical), 480 V maximum.
UL/Non UL compliance
Use the circuit breakers or fuses listed in Table 5.15, to ensure compliance with UL or IEC 61800-5-1.
Circuit breakers must be designed for protection in a circuit capable of supplying a maximum of 10,000 Arms (symmetrical),
480 V maximum.
NOTICE
In the event of malfunction, failure to follow the protection recommendation may result in damage to the frequency
converter.
Circuit Breaker Fuse
UL Non UL UL Non UL
Bussmann Bussmann Bussmann Bussmann Max fuse
Power [kW] Type RK5 Type RK1 Type J Type T Type G
3x200-240 V IP20
0.25
FRS-R-10 KTN-R10 JKS-10 JJN-10 10
0.37 FRS-R-10 KTN-R10 JKS-10 JJN-10 10
0.75 FRS-R-10 KTN-R10 JKS-10 JJN-10 10
1.5 FRS-R-10 KTN-R10 JKS-10 JJN-10 10
2.2 FRS-R-15 KTN-R15 JKS-15 JJN-15 16
3.7 FRS-R-25 KTN-R25 JKS-25 JJN-25 25
5.5 FRS-R-50 KTN-R50 JKS-50 JJN-50 50
7.5 FRS-R-50 KTN-R50 JKS-50 JJN-50 50
11 FRS-R-80 KTN-R80 JKS-80 JJN-80 65
15
Cutler-Hammer
EGE3100FFG
Moeller NZMB1-
A125
FRS-R-100 KTN-R100 JKS-100 JJN-100 125
18.5 FRS-R-100 KTN-R100 JKS-100 JJN-100 125
22
Cutler-Hammer
JGE3150FFG
Moeller NZMB1-
A160
FRS-R-150 KTN-R150 JKS-150 JJN-150 160
30 FRS-R-150 KTN-R150 JKS-150 JJN-150 160
37
Cutler-Hammer
JGE3200FFG
Moeller NZMB1-
A200
FRS-R-200 KTN-R200 JKS-200 JJN-200 200
45 FRS-R-200 KTN-R200 JKS-200 JJN-200 200
Table 5.15 Circuit Breakers and Fuses
How to Install
VLT
®
HVAC Basic Drive FC 101 Design Guide
62 MG18C502 - Rev. 2013-09-06
55