Specifications

Parameter Range Default Function
1-24 Motor Current 0.01-10000.00 A Size related Enter motor current from nameplate data
1-25 Motor Nominal
Speed
100.0-9999.0 RPM Size related Enter motor nominal speed from nameplate data
1-26 Motor Cont. Rated
Torque
0.1-1000.0 Size related
This parameter is available only when 1-10 Motor
Construction Design is set to [1] PM, non-salient
SPM.
NOTICE
Changing this parameter affects
settings of other parameters
1-29 Automatic Motor
Adaption (AMA)
See 1-29 Automatic Motor
Adaption (AMA)
Off Performing an AMA optimises motor performance
1-30 Stator Resistance
(Rs)
0.000-99.990 Size related Set the stator resistance value
1-37 d-axis Inductance
(Ld)
0-1000 Size related Enter the value of the d-axis inductance.
Obtain the value from the permanent magnet
motor data sheet. The de-axis inductance cannot
be found by performing an AMA.
1-39 Motor Poles 2-100 4 Enter the number of motor poles
1-40 Back EMF at 1000
RPM
10-9000 Size related Line-Line RMS back EMF voltage at 1000 RPM
1-73 Flying Start When PM is selected, Flying Start is enabled and
can not disable
1-73 Flying Start [0] Disabled
[1] Enabled
0
Select [1] Enable to enable the frequency converter
to catch a motor spinning due to mains drop-out.
Select [0] Disable if this function is not required.
When is enabled 1-71 Start Delay and 1-72 Start
Function have no function. is active in VVC
plus
mode only
3-02 Minimum Reference -4999-4999 0 The minimum reference is the lowest value
obtainable by summing all references
3-03 Maximum Reference -4999-4999 50 The maximum reference is the lowest obtainable
by summing all references
3-41 Ramp 1 Ramp Up
Time
0.05-3600.0 s Size related
Ramp up time from 0 to rated 1-23 Motor
Frequency if Asynchron motor is selected; ramp up
time from 0 to 1-25 Motor Nominal Speed if PM
motor is selected
3-42 Ramp 1 Ramp
Down Time
0.05-3600.0 s Size related
Ramp down time from rated 1-23 Motor Frequency
to 0 if Asynchron motor is selected; ramp down
time from 1-25 Motor Nominal Speed to 0 if PM
motor is selected
4-12 Motor Speed Low
Limit [Hz]
0.0-400 Hz 0 Hz Enter the minimum limit for low speed
4-14 Motor Speed High
Limit [Hz]
0.0-400 Hz 65 Hz Enter the maximum limit for high speed
4-19 Max Output
Frequency
0-400 Size related Enter the maximum output frequency value
5-40 Function Relay [0]
Function relay
See 5-40 Function Relay Alarm Select the function to control output relay 1
5-40 Function Relay [1]
Function relay
See 5-40 Function Relay Drive running Select the function to control output relay 2
6-10 Terminal 53 Low
Voltage
0-10 V 0.07 V Enter the voltage that corresponds to the low
reference value
How to Programme
VLT
®
HVAC Basic Drive FC 101 Design Guide
72 MG18C502 - Rev. 2013-09-06