Installation manual
© Hills Industries 2009  Page 31 
Data  Default Zone Configuration (Zones 21-31 are not reprogrammable) 
21 
Instant: Partial – Twin Trip – Produces an instant alarm if tripped when armed. Ignored when 
disarmed. This zone will be active in partial mode. This zone type will require two triggers or another 
zone would have to have been trigged before it will activate an alarm. 
22 
Instant: Partial – Group Bypass – Produces an instant alarm if tripped when armed. Ignored when 
disarmed. This zone will be active in partial mode and will be part of the group bypass zones. 
23 
Instant: Twin Trip – Group Bypass – Produces an instant alarm if tripped when armed. Ignored 
when disarmed. This zone will be bypassed in partial mode. This zone type will require two triggers 
or another zone would have to have been trigged before it will activate an alarm. This zone type will 
be part of the group bypass zones. 
24 
Instant: Partial – Twin Trip – Group Bypass – Produces an instant alarm if tripped when armed. 
Ignored when disarmed. This zone will be active in partial mode. This zone type will require two 
triggers or another zone would have to have been trigged before it will activate an alarm. This zone 
type will be part of the group bypass zones. 
25 
Instant: Local – Produces an instant alarm if tripped when armed. Ignored when disarmed. This 
zone will be bypassed in partial mode. This zone will not activate the communicator. 
26 
24 Hour: Audible – A trip on a 24 Hour zone produces an instant alarm when armed or disarmed. 
This zone type will set sirens. 
27 
24 Hour: Silent – A trip on a 24 Hour zone produces an instant alarm when armed or disarmed.
This zone type will not set sirens. 
28 
Fire: – A short on a fire zone will create an alarm condition when the system is armed or disarmed. 
An open will create a Trouble condition. Requires smoke detectors wired Normally Open. Code pad 
zone LED is steady for fire condition and flashing for trouble condition. After a fire activation,
press [*] [7] on the code pad to clear & reset fire zone. Note: 120 seconds of chamber full = alarm. 
29 
Day Zone: – When armed, a trip produces an instant alarm. When disarmed, a trip activates the 
code pad sounder. 
30 
Key-Switch: – A zone attached to a momentary key switch will arm/disarm the panel if the zone is 
momentarily shorted from a sealed condition. A 3.3K resister must be used. Note: If DEOL 
monitoring is enabled in system options, this zone type must have its EOL configuration as all other 
DEOL zones, i.e. two 3.3K resistors must be used to allow full line monitoring for this zone type. 
31 
Chime: – This zone will sound a ding-dong on code pads when unsealed. Alarm activation will 
occur if armed. 
Feature 19    Zone Area Select - Zones 1-8 
Feature 19 is used to select the area(s) that zones 1 - 8 reside in. A zone may reside in any combination of the eight areas.  
If a burglary zone resides in more than one area, it will only be active when all areas it resides in are armed. A zone that 
resides in more than one area will be reported to its lowest area number. Feature 19 has 8 segments. Segment 1 
corresponds to zone 1, and Segment 8 corresponds to zone 8. 
  Area 1  Area 2  Area 3  Area 4  Area 5  Area 6  Area 7  Area 8 
Segment 1 – Zone 1  (1)  2  3  4  5  6  7  8 
Segment 2 – Zone 2  (1)  2  3  4  5  6  7  8 
Segment 3 – Zone 3  (1)  2  3  4  5  6  7  8 
Segment 4 – Zone 4  (1)  2  3  4  5  6  7  8 
Segment 5 – Zone 5  (1)  2  3  4  5  6  7  8 
Segment 6 – Zone 6  (1)  2  3  4  5  6  7  8 
Segment 7 – Zone 7  (1)  2  3  4  5  6  7  8 
Segment 8 – Zone 8  (1)  2  3  4  5  6  7  8 
Zones 9 – 16 Configuration 
Feature 20    Zones 9-16 Configuration Group 
Segments 1-8  16  16  16  16  16  16  16  16 
Feature 20 contains the Configuration Group (zone type) for zones 9-16. Segment 1 is for zone 9, and Segment 8 is for 
zone 16. Refer to the ‘Default Zone Configuration’ table in this section for zone type selections. 










