Hills Reliance Specifications 
Operating Power  16.5 VAC 25, 40, or 50 VA Transformer 
Auxiliary Power   
  W/ 25 VA Transformer  12 VDC Regulated 500 mA 
  W/ 40 or 50 VA 
Transformer 
12 VDC Regulated 1 Amp 
  W/ NX-320 Power Supply  12 VDC Regulated 3.5 Amps 
Loop Resistance   
  Standard Loop  300 Ohms Maximum 
  2-Wire Smokes   30 Ohms Maximum 
  4-Wire Smokes  300 Ohms Maximum 
Loop Response  500mS 
Built-in Siren Driver  3-tone (Steady, Yelp, Evacuation) 
Operating Temperature  0 to 48 degrees C 
LED Code Pad Dimensions  16.25cm Wide 
 10.15cm High 
   2.8cm Deep 
LCD Code Pad Dimensions  16.25cm Wide 
 13.45cm High 
   2.50cm Deep 
Metal Enclosure Dimension  28.60cm Wide 
 28.60cm High 
   8.90cm Deep 
Shipping Weight  4 kg 