Specifications

17 R-407C
AIR COOLED: Performance data at OPTIONAL air ow
MODEL NUMBER DTAD/U-08 DTAD/U-10 DTAD/U-13
ELECTRICAL SECTION Next size motor
Electrical data base on: electric reheat - YES, steam generator - YES, and NEXT SIZE MOTOR.
208-230/3/60 FLA/MCA/MOP 85/103/110 102/122/125 114/137/175
460/3/60 FLA/MCA/MOP 40/49/50 47/56/60 52/63/80
575/3/60 FLA/MCA/MOP 31/38/45 36/43/50 43/51/60
Electrical data base on: electric reheat - NO, steam generator humidi er - YES, and NEXT SIZE MOTOR.
208-230/3/60 FLA/MCA/MOP 60/71/90 77/90/110 89/105/150
460/3/60 FLA/MCA/MOP 29/34/45 36/42/50 41/48/60
575/3/60 FLA/MCA/MOP 22/26/35 27/32/40 34/40/50
Electrical data based on: electric reheat - YES, steam generator humidi er - NO, and NEXT SIZE MOTOR.
208-230/3/60 FLA/MCA/MOP 85/103/110 102/122/125 114/137/175
460/3/60 FLA/MCA/MOP 40/49/50 47/56/60 52/63/80
575/3/60 FLA/MCA/MOP 31/38/45 36/43/50 43/51/60
Electrical data based on: electric reheat - NO, steam generator humidi er - NO, and NEXT SIZE MOTOR.
208-230/3/60 FLA/MCA/MOP 43/51/70 60/70/100 72/85/125
460/3/60 FLA/MCA/MOP 21/25/40 28/33/50 33/39/60
575/3/60 FLA/MCA/MOP 16/19/30 21/24/35 28/33/50
 NEXT SIZE MOTOR
Motor horsepower 5 7.5 7.5
230/3/60 FLA 14.6 23.0 23.0
460/3/60 FLA 6.6 11.0 11.0
575/3/60 FLA 5.3 8.6 8.6
FILTER SECTION
(Pleated, 30% ef cient based on ASHRAE Std. 52.1-1992.)
Quantity/size 3 - 16x25x4 3 - 16x25x4 3 - 16x25x4
CONNECTION SIZES
Liquid line - O.D. copper 5/8 5/8 5/8
Hot gas line - O.D. copper 3/4 3/4 3/4
Condensate drain 3/4 3/4 3/4
Humidi er supply 1/4 1/4 1/4
(Note: Refer to Operation and Maintenance Manual for recommended pipe sizing between unit and condenser section)
FLA - Full load amps
MCA - Minimum circuit ampacity
MOP - Maximum overcurrent protection device amps