DKG-307 User Manual V-01.03 (14.02.2006) Tel: +90-216-466 84 60 Fax: +90-216 364 65 65 datakom@datakom.com.
DKG-307 User Manual V-01.03 (14.02.2006) TABLE OF CONTENTS Section 1. INSTALLATION 1.1. Introduction to the Control Panel 1.2. Mounting the Unit 1.3. Wiring the Unit 2. INPUTS AND OUTPUTS 3. DISPLAYS 3.1. Led Displays 3.2. Digital Display 4. ALARMS AND WARNINGS 5. MODES OF OPERATION 6. OTHER FEATURES 6.1. Remote start operation 6.2. Sender type selection 6.3. Engine heating operation 6.4. Service Request Display 6.5. Engine Hour Meter 6.6. Modem connection 6.7. Remote Monitoring and Programming 6.8.
DKG-307 User Manual V-01.03 (14.02.2006) 1. INSTALLATION 1.1 Introduction to the Control Panel The unit is a control and protection panel used in gensets. It shows the measured values on its displays. The unit is designed to provide user friendliness for both the installer and the user. Programming is usually unnecessary, as the factory settings have been carefully selected to fit most applications. However programmable parameters allow the complete control over the generating set.
DKG-307 User Manual V-01.03 (14.02.2006) 1.3 Wiring the Unit WARNING: THE UNIT IS NOT FUSED. Use external fuses for Mains phases: R-S-T Generator phase: U-V-W Battery positive: BAT(+). Install the fuses as nearly as possible to the unit in a place easily accessible for the user. The fuse rating should be 6 Amps. WARNING: ELECTRICITY CAN KILL ALWAYS disconnect the power BEFORE connecting the unit. 1) ALWAYS remove the plug connectors when inserting wires with a screwdriver.
DKG-307 User Manual V-01.03 (14.02.2006) 2. INPUTS AND OUTPUTS RS-232 SERIAL PORT: This connector provides serial data input and output for various purposes like remote monitoring and remote programming. EXTENSION CONNECTOR: This connector is intended for the connection to output extension modules. The optional relay extension module provides 8 programmable 16A relay outputs. The unit allows the use of up to 2 I/O extension modules.
DKG-307 User Manual V-01.03 (14.02.2006) Term Function 17 RELAY-1 (HORN RELAY) Technical data Output 10A/28VDC 18 RELAY-2 (STOP RELAY) Output 10A/28VDC 19 20 START RELAY FUEL RELAY Output 10A/28VDC Output 10A/28VDC 21 22 23 24 25 26 27 28 29 30 31 32 33 34 EMERGENCY STOP SPARE-2 PROGRAM LOCK SPARE-1 COOLANT LEVEL HIGH TEMP LOW OIL PRESSURE RECTIFIER FAIL CURR_W+ CURR_WCURR_V+ CURR_VCURR_U+ CURR_U- Digital inputs Description This relay has programmable function, selectable from a list.
DKG-307 User Manual V-01.03 (14.02.2006) 3. DISPLAYS 3.1 Led Displays The unit has 29 LEDs, divided in 4 groups: -Group_1: Operating mode: This group indicates the genset function. -Group_2: Mimic diagram: This group indicates the current status of the mains and genset voltages and contactors. -Group_3: Warnings and alarms: This group indicates the existence of abnormal conditions encountered during operation. -Group_4: Unit: This group indicates the unit of the value displayed in the bottom display.
DKG-307 User Manual V-01.03 (14.02.2006) 3.2 Digital Displays The unit has 3 seven segment displays. They show: -Measured parameters, -Service counters, -Statistical counters, -Program parameters. The navigation between different screens in a group is made with the MENU button. Holding the MENU button pressed for 1 second makes the display to switch to the next group.
DKG-307 User Manual V-01.03 (14.02.2006) 4.
DKG-307 User Manual V-01.03 (14.02.2006) 5. MODES OF OPERATION The modes of operation are selected by pushing the front panel keys. Changing the operation mode while the genset is running will result to a behavior suitable for the new operating mode. For example, if the LOAD TEST mode is selected when genset is running at TEST mode, then the genset will take the load. OFF: In this mode, the mains contactor will be energized if mains phase voltages are within the programmed limits.
DKG-307 User Manual V-01.03 (14.02.2006) 6.2 Sender type Selection The unit has the ability to adapt to any type of oil pressure and temperature senders. The commonly used standard sender characteristics are recorded in memory and selectable from a list. However non standard senders may also be used by entering their characteristics to the table. Oil Pressure Sender Type Selection: The oil pressure sender is selected using parameter P_019.
DKG-307 User Manual V-01.03 (14.02.2006) 6.4 Service Request Display This led is designed to help the periodic maintenance of the genset to be made consistently. The periodic maintenance is basically carried out after a given engine hours (for example 200 hours), but even if this amount of engine hours is not fulfilled, it is performed after a given time limit (for example 12 months). The SERVICE REQUEST led has no effect on the genset operation.
DKG-307 User Manual V-01.03 (14.02.2006) 6.7 Remote Monitoring and Programming feature. Thanks to its standard serial RS-232 port, the unit offers the remote monitoring and programming The remote monitoring and www.datakom.com.tr internet site. programming PC software may be downloaded from The software allows the visualization and recording of all measured parameters. The recorded parameters may then be analyzed graphically and printed.
DKG-307 User Manual V-01.03 (14.02.2006) 7. WEEKLY OPERATION SCHEDULE In most applications, the genset is requested to operate only in working hours. Thanks to the weekly program feature unwanted operation of the genset may be prohibited. The unit has one programmable turn-on/turn-off time pairs for each day of week. These programmable parameters allow the genset to operate automatically only in allowed time limits. The weekly operation schedule is only active in AUTO mode.
DKG-307 User Manual V-01.03 (14.02.2006) 8. EVENT LOGGING The unit keeps records of the last 12 events in order to supply information for the service personal. The events are recorded with a date and time stamp. The date and time information comes from the internal battery backed-up real time clock circuit of the unit. The real time clock circuit will continue its operation even in power failures. The real time clock is precisely trimmed using the program parameter P_046.
DKG-307 User Manual V-01.03 (14.02.2006) 10. PROGRAMMING The program mode is used to program the timers, operational limits and the configuration of the unit. To enter the program mode, press the MENU button for 5 seconds. The program mode is only allowed if the PROGRAM LOCK input (terminal_23) is left open. If this input is tied to GROUND, the program value modification will be disabled to prevent unauthorized intervention. It is advised to keep the PROGRAM LOCK input tied to GROUND.
DKG-307 User Manual Pgm Definition V-01.03 (14.02.2006) Unit Std Val 8 Low Freq. Alarm Hz 30 9 Low Freq. Warning Hz 40 10 High Freq. Warning Hz 54 11 High Freq. Alarm Hz 57 V 9.0 V 31.0 V 33.0 12 13 Low Battery Voltage Warning High Battery Voltage Warning 14 High Battery Voltage Alarm 15 Low Oil Pressure Warning Bar 1.5 16 Low Oil Pressure Alarm Bar 1.
DKG-307 User Manual Pgm 21 Definition Hysteresis Voltage V-01.03 (14.02.2006) Unit V Std Val 8 22 Engine Heating Temperature ºC 50 23 Holdoff timer sec 8 24 Overcurrent / Excess Power / Frequency Timer sec 3 25 Wait before Fuel min 0 26 Preheat timer sec 1 27 Start Timer sec 6 28 Wait between Starts sec 10 29 Engine Heating Timer sec 3 30 Mains Waiting Timer min 0.5 31 Cooling Timer min 1.
DKG-307 User Manual Pgm 36 Definition Horn Timer V-01.03 (14.02.
DKG-307 User Manual V-01.03 (14.02.2006) operate automatically from Saturday turn_off time to Monday turn_on time. If the AUTO mode is disabled by the weekly operation schedule, then the AUTO led will flash, otherwise it is steadily on.
DKG-307 User Manual V-01.03 (14.02.2006) Parameters from P_083 to P_130 program the functions of the digital inputs. The programmable properties of digital inputs are: -action to be taken upon arrival of the fault signal (alarm, warning,etc...
DKG-307 User Manual RECTIFIER FAIL INPUT Pgm Description 101 Operation V-01.03 (14.02.
DKG-307 User Manual V-01.03 (14.02.
DKG-307 User Manual V-01.03 (14.02.2006) Parameters from P_143 to P_154 define the ohm-degrees characteristics of the temperature sender. The sender characteristics will be defined using maximum 6 points. The values should be entered in the increasing order of ohm values. For unused points, ohm values should be entered as 0. An example table is given below. The sensor characteristics used in this table are: 38 ºC........342 ohms 82 ºC..........71 ohms 104 ºC........40 ohms 121 ºC........
DKG-307 User Manual V-01.03 (14.02.2006) The parameters from P_155 to P_158 define the exerciser operation. Pgm 155 Definition Exercise start day and hour Unit - Std Val 168 Description This parameter defines the start day and hour of the exerciser. Values higher or equal to 168 mean that the exerciser is off. The exercise may be selected to start at the beginning of the any hour of the week. The parameter value is the hour count of the start time.
DKG-307 User Manual V-01.03 (14.02.2006) 12. TROUBLESHOOTING The genset operates while AC mains are OK or continues to operate after AC mains are OK: -Check engine body grounding. -AC mains voltages may be outside programmed limits, measure the phase voltages. -Check the AC voltage readings by pressing the MENU button. -Upper and lower limits of the mains voltages may be too tight. Check the parameters P_004 and P_005. Standard values are 170/270 volts. -The hysteresis voltage may be given to excessive.
DKG-307 User Manual V-01.03 (14.02.2006) When the AC mains fails, the engine starts to run but the unit gives START FAIL alarm and then the engine stops: -The generator phase voltages are not connected to the unit. Measure the AC voltage between terminals U-V-W and Generator Neutral at the rear of the unit while the engine is running. A fuse protecting the generator phases may be failed. A misconnection may be occurred.
DKG-307 User Manual V-01.03 (14.02.2006) 14. TECHNICAL SPECIFICATIONS Alternator voltage: 0 to 300 V-AC (Ph-N) Alternator frequency: 0-100 Hz. Mains voltage: 0 to 300 V-AC (Ph-N) Current inputs: from current transformers, .../5A. Max load 0.7VA per phase. Digital inputs: input voltage 0 - 30 V-DC. Internally connected to battery positive via 4700 ohm resistor. Analog inputs: Resistor input 0 to 5000 ohms connected to the battery negative. Sources 10 mA when closed to battery negative.
DKG-307 User Manual V-01.03 (14.02.2006) 15.