5. MODES OF OPERATION 
  The modes of operation are selected by pushing the front panel keys. Changing the operation mode 
while the genset is running will result to a behavior suitable for the new operating mode. For example, if the 
LOAD TEST mode is selected when genset is running at TEST mode, then the genset will take the load. 
OFF: In this mode, the mains contactor will be energized if mains phase voltages are within the programmed 
limits. The engine will be stopped. 
AUTO:  It  is  used  for  genset  and  mains  automatic  transfer.  If  at  least  one  of  the  mains  phase  voltages  is 
outside limits (P_004/P_005), the mains contactor will be deactivated. 
The diesel  will  be started  for  programmed  times  (P_035) after  the wait period (P_0026). When the  engine 
runs, the crank relay will be immediately deactivated. The engine will run without load during engine heating 
period (P_029). After this, if alternator phase voltages and frequency are within limits, then the unit will wait for 
the generator contactor period (P_032) and the generator contactor will be energized. 
When all the mains phase voltages are within the limits, the engine will continue to run for the mains waiting 
period (P_030). At the end of this period the generator contactor is deactivated and the mains contactor will be 
energized. If a cooling period is given (P_031), the generator will continue to run during cooling period. At the 
end of the period, the fuel solenoid will be de-energized and the diesel will stop. The unit will be ready for the 
next mains failure. 
If  the  operation  of  the  genset  is  disabled  by  the  weekly  schedule,  then  the  AUTO  led  will  flash,  and  the 
operation of the genset will be as in the OFF mode. 
TEST: It is used to test the generator when the mains are on, or keep the generator running in the emergency 
backup mode (P_041). The operation of the generator is similar to the AUTO mode, but the mains contactor 
will not be deactivated if the mains are not off. If the mains are off, mains contactor will be deactivated and the 
generator contactor will be activated. When the mains are on again, a changeover to the mains will be made, 
but the engine will be kept running unless another mode is selected. To stop the engine, select AUTO or OFF 
mode. 
LOAD TEST: It is used to test the genset under load. Once this mode is selected, the engine will run and the 
load  will  be  transferred  to  the  genset.  The  genset  will  feed  the  load  indefinitely  unless  another  mode  is 
selected. 
6. OTHER FEATURES 
6.1 Remote Start Operation 
The unit offers the possibility of REMOTE START mode of operation. If the program parameter 
P_042 is set to 1 then the unit will enter to the Remote Start operation. The Remote Start signal should be 
connected to the SPARE_2 (22) input. 
  The REMOTE START signal may be a NO or NC contact, switching to either battery positive or 
battery negative. These selections are made using programming menu. 
  In this mode the mains phases are not monitored. If the REMOTE START signal is present then 
the mains will be supposed to fail, inversely if the REMOTE START signal is absent, then mains voltages 
will be supposed to be present. The front panels mimic diagram’s mains LEDs will reflect the status of the 
REMOTE START input. 