10. PROGRAMMING 
The program mode is used to program the timers, operational limits and the configuration of the unit.  
To enter the program mode, press the MENU button for 5 seconds. The program mode is only 
allowed  if  the  PROGRAM  LOCK  input  (terminal_23)  is  left  open.  If  this  input  is  tied  to  GROUND,  the 
program value modification will be disabled to prevent unauthorized intervention. It is advised to keep the 
PROGRAM LOCK input tied to GROUND. 
The program  mode  will  not  affect the  operation of  the unit.  Thus  programs  may  be  modified 
anytime, even while the genset is running. 
When the  program mode is  entered, the  upper  display  will show  “PGM”. The  central display  will 
show the program parameter number and the lower display the program parameter value. The first 
program number is “000” 
Each depression of the MENU key will cause the display to switch to the next program parameter. 
If the MENU key is hold pressed the program numbers will increase by steps of 10. After the last 
parameter, the  display switches back to  the first parameter.    The  displayed  parameter value  may  be 
increased or decreased using “” and “” keys. If these keys are hold pressed, the program value will be 
increased/decreased by steps of 10. 
  Program parameters are kept in a non-volatile memory and are not affected from power failures. 
To exit the program mode press one of the mode selection keys. If no button is pressed during 1 
minute the program mode will be cancelled automatically. 
Pgm  Definition  Unit  Std Val  Description 
0 
Current Transformer 
Primary 
A  500 
This is the rated value of current transformers. 
All transformers must have the same rating. 
The secondary of the transformer will be 5 
Amps. For values over 990A use 10% of the 
value. These values will be displayed as K-
Amperes. (for ex. 1.85KA) Values under 100A 
may be used by multiplying with 10 in order to 
enable the current display with 0.1A precision. 
(for ex: 35.7A) 
1 
Current Transformer 
Decimal Point 
  0 
This parameter determines the display range of 
current and active power: 
0: 000-999 
1: 0.00-9.99 
2: 00.0-99.9 
2  Overcurrent Limit  A  500 
If the current goes above this limit, during the 
period defined in P_024 an OVERLOAD alarm 
will be generated. Enter this information with the 
same format as parameter P_000. 
3  Excess Power Limit  KW  350 
If the active power goes above this limit, during 
the period defined in P_024 an OVERLOAD 
alarm will be generated. Enter this information 
with the same format as parameter P_000. 
4  Mains Voltage Low Limit  V  170 
If one of the mains phases goes under this 
limit, it means that the mains are off and it 
starts the transfer to the genset in AUTO and 
TEST modes. 
5  Mains Voltage High Limit  V  270 
If one of the mains phases goes over this limit, 
it means that the mains are off and it starts the 
transfer to the genset in AUTO and TEST 
modes. 
6  Gen. Voltage Low Limit  V  180 
If one of the generator phase voltages goes 
under this limit when feeding the load, this will 
generate a VOLTAGE alarm and the engine will 
stop. 
7  Gen. Voltage High Limit  V  270 
If one of the generator phase voltages goes over 
this limit when feeding the load, this will generate 
a VOLTAGE alarm and the engine will stop. 