User manual
DKG-307 User Manual V-01.03 
(14.02.2006)
      - 4 - 
1.3 Wiring the Unit 
WARNING: THE UNIT IS NOT FUSED. 
Use external fuses for 
Mains phases: R-S-T 
Generator phase: U-V-W 
Battery positive: BAT(+). 
Install the fuses as nea
rly as possible to       
the unit in a place easily accessible for the user. 
The fuse rating should be 6 Amps.
WARNING: ELECTRICITY CAN KILL 
 ALWAYS disconnect the power BEFORE connecting the unit.
1)  ALWAYS remove the plug connectors when inserting wires with a screwdriver. 
2)  ALWAYS refer to the National Wiring Regulations when conducting installation.
3)  An appropriate and readily accessible set of disconnection devices (e.g. 
automatic fuses) MUST be provided as part of the installation. 
4)  The disconnection device must NOT be fitted in a flexible cord. 
5)  The building mains supply MUST incorporate appropriate short-circuit backup 
protection (e.g. a fuse or circuit breaker) of High Breaking Capacity (HBC, at 
least 1500A). 
6)  Use cables of adequate current carrying capacity (at least 0.75mm
2
) and 
temperature range. 