User manual
DKG-307 User Manual V-01.03 
(14.02.2006)
      - 6 - 
Term  Function  Technical data  Description 
17  RELAY-1 (HORN RELAY) 
Output 10A/28VDC  This  relay  has  programmable  function, 
selectable from a list. 
18  RELAY-2 (STOP RELAY) 
Output 10A/28VDC  This  relay  has  programmable  function, 
selectable from a list.  
19  START RELAY 
Output 10A/28VDC  This relay controls the engine cranking. 
20  FUEL RELAY 
Output 10A/28VDC  This relay is used for fuel solenoid control. It is 
internally  connected  to  terminal  16  for 
supplying  the  charge  alternator’s  excitation 
current. 
21  EMERGENCY STOP 
22  SPARE-2 
23  PROGRAM LOCK 
24  SPARE-1 
25  COOLANT LEVEL 
26  HIGH TEMP 
27  LOW OIL PRESSURE 
28  RECTIFIER FAIL 
Digital inputs  These  inputs  have  programmable 
characteristics  selected  via  the  program 
menu.  Each  input  may  be  driven  by  a 
‘normally closed’ or ‘normally open’ contact, 
switching  either  battery+  or  battery-.  The 
effect  of  the  switch  is  also  selectable  from  a 
list. See PROGRAMMING section  for  more 
details. 
29  CURR_W+ 
30  CURR_W- 
31  CURR_V+ 
32  CURR_V- 
33  CURR_U+ 
34  CURR_U- 
Current  transformer 
inputs, 5A-AC 
Connect the generator current transformer 
terminals to these inputs. Do not connect the 
same current transformer to other instruments 
otherwise a unit fault will occur. Connect each 
terminal of the transformer to the unit’s related 
terminal. Do not use common terminals. Do 
not use grounding. Correct polarity of 
connection is vital. If the measured power is 
negative, then change the polarity of each 3 
current transformers. The rating of the 
transformers should be the same for each of 
the 3 phases. The secondary winding rating 
shall be 5 Amperes. (For ex. 200/5 Amps).  