DX8200A Reference Manual
DX8200A REFERENCE MANUAL
DATALOGIC S.p.A. Via Candini 2 40012 - Lippo di Calderara di Reno Bologna - Italy DX8200A Reference Manual Ed.: 07/2006 ALL RIGHTS RESERVED Datalogic reserves the right to make modifications or improvements without prior notification. Datalogic shall not be liable for technical or editorial errors or omissions contained herein, nor for incidental or consequential damages resulting from the use of this material.
CONTENTS REFERENCES ............................................................................................................. v Reference Documentation ............................................................................................ v Services and Support ................................................................................................... v COMPLIANCE.............................................................................................................
2.5.6 2.6 2.6.1 2.6.2 3 3.1 3.2 3.2.1 3.2.2 3.2.3 3.3 3.4 4 4.1 4.1.1 4.2 4.2.1 Large Synchronized Network...................................................................................... 35 Redundant System ..................................................................................................... 37 Multidata Network ....................................................................................................... 38 Fieldbus Network .................................................
REFERENCES REFERENCE DOCUMENTATION The documentation related to the DX8200A management is listed below: • C-BOX 100 Installation Manual • PWR series power supply unit Installation Manuals • PWO power supply unit Installation Manual • SC6000 Controller Reference Manual • Document about the Ethernet connectivity • Help On-Line in PDF format SERVICES AND SUPPORT Datalogic provides several services as well as technical support through its website. Log on to www.datalogic.
COMPLIANCE ELECTRICAL SAFETY This product conforms to the applicable requirements contained in the European Standard for electrical safety EN-60950 at the date of manufacture. This symbol refers to operations that must be performed by qualified personnel only. Example: opening the device. WARNING This symbol refers to operations where there is danger of electrical shock. Before opening the device make sure the power cable is disconnected to avoid electric shock.
Warning labels indicating exposure to laser light and the device classification are applied onto the body of the scanner (Figure A): LASER LIGHT DO NOT STARE INTO BEAM CLASS 2 LASER PRODUCT MAXIMUM OUTPUT RADIATION 1 mW EMITTED WAVELENGTH 630~680 nm TO EN 60825-1:2001 DATALOGIC S.P.A. Via Candini, 2 40012 Calderara di Reno - Bologna - Italy CAUTION-CLASS 3B LASER LIGHT WHEN OPEN AVOID EXPOSURE TO BEAM Manufactured Volt Model No. Amp. Serial No.
LINE FUSE REPLACEMENT (VAC MODELS ONLY) CAUTION Caution – double pole/neutral fusing. For continued protection against risk of fire, replace with same type and rating of fuse (250V, 3.15 A).
GENERAL VIEW DX8200A 1 2 2 3 4 1 Laser Beam Output Windows 3 Laser Safety Label 2 Mounting Slots 4 Mounting Reference Label Figure A - DX8200A – Reading Windows Side 1 4 2 3 1 Connector Panel 3 Product Label 2 Service Access Cap 4 Display and Keypad Panel Figure B - DX8200A Display and Keypad Side ix
1 7 2 3 4 5 6 Figure C – Display and Keypad Panel 1 Programming Keypad 5 TX Data LED (Green) 2 Power On LED (Green) 6 Network LED (Red) 3 Phase On LED (Yellow) 7 LCD Display 4 Encoder LED (Yellow) 1 3 2 Figure D – Connector Panel for Standard Models 1 Lonworks 17-pin male connector 2 Lonworks 17-pin female connector 3 Serial interface and I/O 26-pin connector 1 4 2 3 Figure E – Connector Panel for Ethernet Models x 1 Lonworks 17-pin male connector 3 Serial interface and I/
1 4 2 3 Figure F – Connector Panel for Profibus Models 1 Lonworks 17-pin male connector 3 Serial interface and I/O 26-pin connector 2 Lonworks 17-pin female connector 4 Profibus 9-pin female connector 1 4 2 3 Figure G – Connector Panel for DeviceNet Models 1 Lonworks 17-pin male connector 3 Serial interface and I/O 26-pin connector 2 Lonworks 17-pin female connector 4 DeviceNet 5-pin male connector 4 1 3 2 Figure H –Input Power Module (VAC Models only) 1 Line Fuse 3 Power Inlet 2 L
GUIDE TO INSTALLATION POINT-TO-POINT INSTALLATION The following can be used as a checklist to verify all the necessary steps to complete installation of the DX8200A scanner. 1) Read all information in the section “Safety Regulations” at the beginning of this manual. 2) Correctly mount the scanner according to the information in par. 2.2.1 and position it at the correct reading distance as shown in par. 4.4.
MASTER/SLAVE LONWORKS INSTALLATION The following can be used as a checklist to verify all the steps necessary to complete installation of the DX8200A scanner in a Master/Slave Lonworks network. 1) Read all information in the section “Safety Regulations” at the beginning of this manual. 2) Correctly mount the scanner according to the information in par. 2.2.1 and position it at the correct reading distance as shown in par. 4.4.
8) Optionally, perform the ASR Network Configuration procedure for system backup purposes (see par. 5.2.1). 9) Exit the configuration program and run your application. The installation is now complete.
INTRODUCTION 1 1 INTRODUCTION 1.1 PRODUCT DESCRIPTION The DX8200A scanner is a barcode reader complete with decoder designed to provide an innovative and high performance solution in omnidirectional reading applications by combining the following advanced technologies with Datalogic solid experience in the material handling sector. Some of the main features of DX8200A are listed below: • scanning speed 1000 scans/sec. (500 scans for each line). • reads all popular codes.
DX8200A 1 Feature Benefit ACR™ • Advanced Code Reconstruction technology allows the reading of low aspect ratio labels placed anywhere on a parcel and enhances the readability of poorly printed or damaged codes. CD SQUARE™ • CD SQUARE™ provides useful information on label position and object shape elaborated during the barcode reading phase. This innovative technology identifies the area in which the code is located and measures the code distance from the scanner.
INTRODUCTION 1 1.3 MODEL DESCRIPTION The DX8200A scanner is available in versions that differ depending on the interface connection, the optical resolution and on the input power type: DX8200A - 3 X Y Z Power: 0 = VDC 1 = VAC Communication Type: Optical Resolution: 0 = Standard version 1 = Ethernet version 2 = Profibus version 3 = DeviceNet version 1 = Medium resolution 2 = High resolution 3 = Very High resolution 1.4 INDICATORS The DX8200A has five LEDs on the rear panel.
DX8200A 1 1.
INSTALLATION 2 2 INSTALLATION To install the system follow the given procedure: 1. Select the mounting location for DX8200A; 2. Mount the DX8200A scanner; 3. Position the scanner with respect to the barcode; 4. Proceed with system electrical connection; 5. Install the Genius™ program on the PC and configure the scanner.
DX8200A 2 2.2 MECHANICAL MOUNTING 2.2.1 Mounting the Scanner DX8200A can be installed to operate in any position. There are 4 slots (dia. 8.5 mm) on the sides of the scanner for mounting. The diagram below can be used for installation; refer to par. 4.4 for correct positioning of the scanner with respect to the reading zone and scanner orientation. See par. "Scanner Direction" for scanner direction relative to the conveyor. PackTrack™ Coordinate Reference Point where x, y, z = 0 470 [18.50] = 8.
INSTALLATION 2 2.
DX8200A 2 The table below gives the pinout of the C-BOX 100 terminal block connectors.
INSTALLATION 2.3.1 2 Main/Aux. Serial Interface and I/O Connector The DX8200A Standard and Fieldbus models are equipped with a 26-pin male D-sub connector for connection to the host computer, power supply and input/output signals.
DX8200A 2 Main Interface The main serial interface is compatible with the following electrical standards: RS232 RS485 half-duplex RS485 full-duplex (20 mA current loop) The 20 mA Current Loop interface is available by using the C-BOX 100 with the optional INT-30 accessory installed in it. The scanner communicates to the C-BOX 100 through the RS232 interface and the INT-30 converts the signals. The main serial interface type and its relative parameters (baud rate, data bits, etc.
INSTALLATION 2 RS485 Full-Duplex Interface The RS485 full-duplex interface is used for non-polled communication protocols in point-to-point connections over longer distances than those acceptable for RS232 communications or in electrically noisy environments. The overall maximum cable length should not exceed 1200 m (3937 ft).
DX8200A 2 RS485 Half-Duplex Interface The RS485 half-duplex interface can be used for multidrop connections with a Datalogic multiplexer or it can also be used for a master/slave layout. The overall maximum cable length should not exceed 1200 m (3937 ft).
INSTALLATION 2 Inputs The inputs of the reader are on the 26-pin connector of the DX8200A. These inputs are called EXT_TRIG/PS, IN2/ENC, IN3 and IN4.
DX8200A 2 DX8200A EXTERNAL TRIGGER/ENCODER Vext A/B + 5V ~ V - + ~ B/A Ground Figure 10 - NPN Command Input Connection using External Power DX8200A EXTERNAL TRIGGER/ENCODER VS A/B + 5V ~ + V - ~ B/A GND Ground Figure 11 - NPN Command Input Connection using Scanner Power Vext DX8200A EXTERNAL DEVICE V IN3A + 5V ~ + - ~ Ground Vext V IN4A + 5V ~ + ~ - INREF Ground Figure 12 – IN3/IN4 PNP Input Command using External Power 14
INSTALLATION 2 DX8200A EXTERNAL DEVICE VS INREF + 5V ~ + V - ~ IN3A Ground EXTERNAL DEVICE + 5V ~ + V - ~ IN4A GND Ground Figure 13 - IN3/IN4 NPN Input Command using Scanner Power Input devices can be supplied by either scanner power (VS and GND) or external power supplies (Vext). Electrical isolation between the input command logic and the scanner is maintained when powering the input devices from an external supply voltage (Vext).
DX8200A 2 Outputs Three general purpose outputs are available. Pin 8 22 11 12 16 17 Name OUT 1+ OUT 1OUT 2+ OUT 2OUT 3A OUT 3B Function Configurable digital output 1 – positive pin Configurable digital output 1 – negative pin Configurable digital output 2 – positive pin Configurable digital output 2 – negative pin Configurable digital output 3 – polarity insensitive Configurable digital output 3 – polarity insensitive The function of the three outputs OUT1, OUT2 and OUT3 can be defined by the user.
INSTALLATION 2 The OUT3 electrical features are given below: Maximum voltage ± 100 V Collector current (pulse) 240 mA Max. Collector current (continuous) 150 mA Max. R on 6 – 15 Ω R off > 500 Ω Off-state leakage current < 1 µA Maximum power dissipation 550 mW at 50°C (Ambient temperature). DX8200A USER INTERFACE Vext 100 Vdc max A/B B/A Figure 15 – Output 3 Interface The command signal is filtered and generates a delay of about 50 µs for OUT1 and OUT2 and 1 ms for OUT3. 2.3.
DX8200A 2 Network Termination When building a Lonworks system the network must be properly terminated by positioning the BTK-8102 Lonworks terminator in the DX8200A master reader and the BTK-8100 Lonworks bus return in the last DX8200A slave reader.
INSTALLATION 2 Lonworks Interface The Lonworks network is used for both input and output connection to build a multi-sided or omni-station system connecting several readers. The DX8200A master usually employs the 17-pin female connector for output connection to the first slave, while the 17-pin male connector is terminated by inserting the BTK-8102 terminator (see Figure 17 for details). Both connectors are always employed when connecting together the slave readers.
DX8200A 2 The following diagrams represent different network terminations using either the BTK-8102 Lonworks terminator or the BTK-8100 bus return. In Figure 21 the BTK-8102 terminator is indicated by the element, while the figure below shows its electrical circuit in details: Figure 20 – BTK-8102 Electrical Circuit The diagram below represents the termination of the double Lonworks line of a DX8200A working as master by means of the BTK-8102.
INSTALLATION 2.3.3 2 Ethernet Connector This connector is only available for DX8200A Ethernet models and allows the Ethernet connection between the host and the reader. Figure 23 – Harting RJ Industrial® Push Pull Male Connector 1 8 Figure 24 – DX8200A Harting RJ Industrial® Female Connector This interface and the connector pinout (see the following table) are IEEE 802.3 10 BaseT and IEEE 802.3u 100 Base Tx compliant. RJ45 Modular Jack Pinout Pin 1 2 3 6 4, 5, 7, 8 Name TX + TX RX + RX N.C.
DX8200A 2 Ethernet Interface The Ethernet interface (NIC) can be used for TCP/IP communication with a remote or local host computer by connecting the scanner to a LAN. It can also be connected directly to a host PC. The following is an example of a connection to a LAN through a Hub using a straight through cable: HUB / SWITCH DX8200A TX+ 1 1 TX- 2 2 RX+ 3 3 n. c. 4 4 n. c. 5 5 RX- 6 6 n. c. 7 7 n. c. 8 8 n. c.
INSTALLATION 2.3.
DX8200A 2 2.3.5 Profibus Connector The 9-pin Profibus female connector (white) is only available in the DX8200A Profibus model and allows connection between the host and the reader: 1 5 9 6 Figure 28 - Profibus 9-pin Female Connector DX8200A 9-pin Profibus connector pinout Pin 1 2 3 4 5 6 7 8 9 * ** Name Shield* Free B-LINE (RxD/TxD-P) CNTR-P** DGND +5 V Free A-LINE (RxD/TxD-N) CNTR-N** Function Shield, Protective Ground resp.
INSTALLATION 2 Note that GND is internally connected to chassis. The cable shield is also connected to pin 1 - CHASSIS. DX8200A USER INTERFACE VS 9/13 23/25 GND 1 CHASSIS V+ (20 – 30 Vdc) V- (Ground) Chassis Earth Ground Figure 29 – Power Supply Using the 26-pin Connector Vac models: The supply voltage for correct operation of the scanner must be between 110 and 230 VAC. The max. power consumption is 35 VA including startup current.
DX8200A 2 2.5 TYPICAL LAYOUTS The DX8200A scanners can be connected in a variety of layouts depending on the number of scanners used and the required complexity of the reading station. These layouts range from Single Stand Alone to Complex Lonworks Networks. Vac models can be used for point-to-point connections eliminating the need for an external PWR power supply.
INSTALLATION 2 In general, for all point-to-point layouts, DX8200A Vac models can substitute the Vdc model and therefore eliminate the PWR power supply. This requires that the C-BOX 100 must be modified to accept scanner power for the P.S. Standard CAB601X C-BOX 100** 110 - 230 Vac Local Host Presence Sensor* * P.S. (Presence Sensor) connected to External Trigger/PS input.
DX8200A 2 2.5.2 Pass Through When Pass Through is activated on the Auxiliary interface, the DX8200A reader can be integrated in a network consisting of different scanners not provided with a Lonworks interface. This connection mode allows two or more devices to be connected to a single external serial interface. The DX8200A transmits the messages received by its auxiliary interface onto its main interface.
INSTALLATION 2 PLC Host P.S.* P.S.* Gryphon Fieldbus Network DX8200A DS4600A DS4600A CAB601X C-BOX 100 C-BOX 100 C-BOX 100 AUX P.S.* 2 1 2 1 PWR-120 1 * Main Serial Interface 2 Auxiliary Serial Interface Presence Sensor connected to External Trigger/PS input. Figure 34 – Pass Through Connection for Fieldbus Models 2.5.
DX8200A 2 CAB601X DS4600A Slave 1 1 C-BOX 100 DX8200A Master AUX MAIN P.S.* 2 Local Host 1 2 C-BOX 100 DS4600A Slave 2 PWR-120 C-BOX 100 1 1 * 2 Main Serial Interface Auxiliary Serial Interface P.S. (Presence Sensor) connected to External Trigger/PS input. Figure 35 – RS232 Master/Slave for DX8200A Standard Models Remote PLC DX8200A Master CAB601X Fieldbus Network C-BOX 100 AUX DS4600A Slave 2 P.S.
INSTALLATION 2.5.4 2 Multiplexer The Multiplexer connection is used to integrate a DX8200A slave reader in a Multidrop network consisting of different scanners not provided with a Lonworks interface. Each scanner is connected half-duplex main interface. P.S.* to a Multiplexer (MX4000) with the RS485 P.S.* P.S.* DX8200A < DS4600A < DS4600A EN T < < EN T C-BOX 100 C-BOX 100 #31 #1 PWR-120 C-BOX 100 MX4000 1 #0 Local Host 1 * RS485 HD Main Interface P.S.
DX8200A 2 2.5.5 Local Lonworks Network A local Lonworks network allows logically connecting a DX8200A master reader with up to 31 DX8200A slaves. Actually, the maximum number of readers to be employed in the network depends on the system operating conditions; that is adopted operating mode and amount of data stream.
INSTALLATION 2 Small Synchronized Network When building a small local Lonworks network (less than 10 scanners), the DX8200A master reader must be connected to a local host computer or a C-BOX 100 by means of a CAB-601X cable connected to the 26-pin D-sub male connector. The master reader connects to the first slave reader of the system through the local Lonworks 17-pin female connector.
DX8200A 2 The following image shows a system consisting of five readers where the external signals (trigger, encoder, serial to host, etc.) are connected to the master through the C-BOX 100. The system is powered by the PWR-240 where: • the master is connected through CAB-860X, which also provides bus termination • the last slave is connected through CAB-830X, which also provides bus return.
INSTALLATION 2 Large Synchronized Network When building a large local Lonworks network (more than 10 scanners), an SC6000 Controller must be used together with a PWO power supply/junction box unit. In this case the SC6000 unit acts as the system master and is connected to the host through one of its interfaces. All scanners act as slaves and are connected to the SC6000 through the PWO power supply/junction box.
DX8200A 2 SC6000 Conveyor Figure 41 - Large Synchronized Network Reading Station 36
INSTALLATION 2 Redundant System For large local Lonworks networks, a redundant system can per configured in which two SC6000 Controllers are used together with their respective PWO power supply/junction box units. The scanners are distributed equally between the PWO units. In this case one of the SC6000 Controllers is dedicated as the working or active unit while the other functions as a dedicated protecting or backup unit.
DX8200A 2 Multidata Network In this layout, one master and up to 7 DX8200A slave readers have their own P.S. and therefore multiple reading phases. Each P.S. is connected through a C-BOX 100, which in turn is connected to its relative scanner through a CAB-601X cable. The master sends all the individual messages collected from the Lonworks interface as well as its own to the Local Host through its C-BOX 100.
INSTALLATION 2.5.6 2 Fieldbus Network The Fieldbus models offer connectivity without any converter or adapter needed. The DX8200A master Fieldbus communicates with a remote host (for ex. remote PC connected via Internet) by means of a cable connected to the Fieldbus connector provided. It can be activated by a signal generated by the remote Host or by a physical presence sensor. The external signals (trigger, encoder) are connected to the master through the C-BOX 100.
DX8200A 2 2.
SOFTWARE CONFIGURATION 3 3 SOFTWARE CONFIGURATION 3.1 GENIUS™ INSTALLATION Genius™ is a new Datalogic scanner configuration tool providing several important advantages: • Wizard approach for low skilled users; • Multi-language version; • Defined configuration directly stored in the reader; • Communication protocol independent from the physical interface allowing to consider the reader as a remote object to be configured and monitored.
DX8200A 3 After defining the parameter values the following window appears allowing to complete the reader configuration as follows: - Saving the configuration to disk; - Switching to Advanced mode; - Sending the configuration to the scanner. Figure 46 - Genius™ Wizard Closing Window Test Operating Mode This operating mode is not available when DX8200A works as Slave.
SOFTWARE CONFIGURATION 3 On Line Operating Mode Figure 48 - On Line Mode Selection This operating mode causes the reader to be connected to an external Presence Sensor using EXT TRIG/PS A and EXT TRIG/PS B inputs. During the active phase of the presence sensor, the DX8200A reader tries to acquire and correctly decode the code. In case the decoding phase is successful, the barcode characters are transmitted on the serial interface. Otherwise, a no read message is sent.
DX8200A 3 3.2.2 Genius™ Network Setup Through Master Network Setup allows configuring your Local Lonworks Network through the Master using Genius™. Three different procedures are available to define the number of network slave scanners, their label and address according to two main conditions: Condition Available Procedure Feature Unknown Slave Addresses Net-Autoset automatically assigns random addresses to slave or Stand Alone scanners.
SOFTWARE CONFIGURATION 3 The following dialog box appears asking whether to send the configuration to the Master or not: icon available on the Toolbar to make the 2. Click the "Yes" button, then click on the “Devices” area appear next to the Parameter Explorer window. By repeatedly clicking the icon this area will be displayed or hidden.
DX8200A 3 3. Then, proceed with the network setup by using one of the icons available on the Tool Bar according to the procedure to follow: = Net-Autoset procedure = Network Wizard procedure = Express Network Setup procedure Net-Autoset This procedure is to be used when all scanner addresses and labels are unknown (typically when configuring the network for the first time or whenever a network reconfiguration is required).
SOFTWARE CONFIGURATION 3 Network Wizard Before performing this procedure, a Lonworks address must be assigned to each slave scanner. The most practical method is through the Net-Autoset procedure. See par. 3.2.3 for alternative address assignment methods. Once all addresses have been assigned, the Network Wizard is to be used when one or more scanner addresses and labels need to be modified. 1. Click on the button to open the Network Wizard dialog box: a.
DX8200A 3 2. If desired, select a slave scanner within the "Current Devices" area and click on the icon (or select the "Show Device" option from the right-click menu) to make the dialog box appear as follows: • • The "Show Device" option is particularly useful after the Net-Autoset procedure or whenever it is necessary to know which address is assigned to a specific slave scanner.
SOFTWARE CONFIGURATION 3.2.3 3 Alternative Slave Address Assignment As alternatives to Network Setup through the Master, each Slave scanner can be assigned an address through the following methods: • address setting through the Local Device Network Settings item in the Device Menu with the slave scanner connected to Genius™ • manual address setting through slave scanner keyboard (see par. 2.6.1 for details) 3.
DX8200A 3 3.4 PARAMETER DEFAULT VALUES The following table contains the list of the factory default settings for the DX8200A. Genius™ also allows checking the parameter default values by selecting the "Compare parameters" option available in the Tools menu and comparing the current scanner configuration to the default one.
SOFTWARE CONFIGURATION Parameter Reading Parameters Beam Shutter Overflow Start Ratio Overflow Stop Ratio Reading Mode Reading Condition Reconstruction Parameters Enabled Stacked Code Extended Min Match Position Tolerance Duration Tolerance Min Start/Stop Number Inter Char Gap Addon Overflow Ratio Scan Line Amplitude Amplitude Settings Enable PackTrack Calibration Direction PS Offset Data Communication Settings Host Application Protocol Type Data Format Header TX Start Termination After No Read Message Mes
DX8200A 3 Parameter Parameters Stop Bits Auxiliary Serial Port Data Tx Heartbeat Pass Through Parameters Baud Rate Parity Data Bits Stop Bits Digital I/O Setting Digital Input Lines Setting Debouncing For Input 1, 3 and 4 Debouncing For Input 2 Input 1 Active Level Overridden by Op. Mode Input 2 Active Level Overridden by Op. Mode Input 3 Active Level Overridden by Op. Mode Input 4 Active Level Overridden by Op.
SOFTWARE CONFIGURATION Parameter Diagnostics PackTrack Debug Message Tx Enable Statistics 3 Default Setting Disabled (unchecked) Unchecked Disabled (unchecked) 53
DX8200A 4 4 READING FEATURES 4.1 ADVANCED CODE RECONSTRUCTION (ACR™ 4) The traditional way of barcode reading could be called “Linear Reading”. In this case, the laser beam crosses the barcode symbol from its beginning to its end as shown in the following figure: Laser Beam Figure 53 – Linear Reading In Advanced Code Reconstruction mode it is no longer necessary for the laser beam to cross the label from the start to the end.
READING FEATURES 4 The decoder will be able to read the label with a tilt angle between + α max and - α max as shown in the following figure: 0° OK OK Conveyor -α +α OK No Read No Read No Read OK OK Laser Beam Figure 56 – Reading Zones with α Max The formulas to calculate α maximum depend on various parameters such as: label height, number of scans per second, code motion speed, etc.
DX8200A 4 Figure 58 – PackTrack™ System Layout Working in PackTrack™ mode requires the presence of an encoder and a presence sensor to track the moving packs. All PackTrack™ functionalities are programmed via the Genius™ tool (refer to the Genius™ Help On-Line for details).
READING FEATURES 4 For DX scanners the zero coordinate references are located on the scanner. PackTrack™ Coordinate Reference Point where x, y, z = 0 Figure 60 – DX8200A Coordinate Reference Point 4.2.1 PackTrack™ Calibration for DX8200A The DX8200A scanner calibration is already made at the factory and it is not recommended to overwrite it. By means of the Genius™ software tool SPY, the user can set the Direction and PS Offset parameters.
DX8200A 4 Once the Spy window has been opened, select the “PackTrack™ Calibration” option from the Tools menu: Figure 62 – Selecting PackTrack™ Calibration Option The following window will open: Figure 63 – PackTrack™ Calibration Window Set the PS Offset and Direction parameters.
READING FEATURES 4 Top View Conveyor Direction DX8200A Scanner Direction 90° Top View Conveyor Direction DX8200A Scanner Direction 180° (Reverse) Top View Conveyor Direction DX8200A Scanner Direction 270° 59
DX8200A 4 4.2.2 Overwriting PackTrack™ Calibration for DX8200A Only necessary for special circumstances, it is possible to overwrite the factory scanner calibration by clicking on the “Calibrate DX” button shown in the figure above.
READING FEATURES 4 Leg 1 Leg 2 Figure 65 – DX8200A Scan Legs In the vast majority of systems the x and z data are not necessary. For these cases set x = 0, z= 0 during the calibration procedure. NOTE 4.3 PERFORMANCE The scan rate is 1000 scans/sec (500 scans on each leg). Refer to the diagrams in par. 4.4 for further details on the reading features. These diagrams are taken on various resolution sample codes at a 25 °C ambient temperature depending on the conditions listed under each diagram.
DX8200A 4 4.3.1 • • Reading Conditions ANSI Grade B minimum 500 scans/sec per leg The following tables describe the requirements for standard applications. Minimum Code Height for Omnidirectional Reading (mm) Conveyor Speed (m/s) 0.5 1 1.5 2 2.5 11 13 15 17 19 0.25 12 14 16 18 20 0.30 2/5 Interleaved 13 15 17 19 21 0.33 Code Resolution 14 16 18 20 23 0.38 (mm) 18 19 22 24 26 0.50 24 26 27 29 32 0.72 33 34 35 37 39 1.
READING FEATURES 4 Minimum Code Height for Omnidirectional Reading (mm) Conveyor Speed (m/s) 0.5 1 1.5 2 2.5 8 10 12 14 16 0.25 9 11 13 15 17 0.30 Codabar 9 11 13 15 18 0.33 Code Resolution 10 12 14 16 18 0.38 (mm) 13 14 16 18 20 0.50 17 18 19 21 24 0.72 23 24 25 26 28 1.00 3 18 19 20 20 22 26 30 Ratio 3:1; Interdigit = Module Size Table 4 Minimum Code Height for Omnidirectional Reading (mm) Conveyor Speed (m/s) 0.5 1 1.5 2 2.5 8 9 11 13 15 0.25 9 10 12 14 16 0.30 EAN 8-13, UPC-A 9 10 12 14 16 0.
DX8200A 4 4.4 READING DIAGRAMS DX8200A-3X3X (0.25 mm/10 mils) The diagram shows an average reading area obtained considering different barcode types of variable quality. z x -20 -50 -16 -40 -12 -30 -8 -20 -4 -10 0 0 4 10 8 20 12 30 16 40 0 -16 -24 -32 -40 0 -40 -60 -80 -100 -48 (in) -120 50 20 (in) (cm) Note: x = 0 and z = 0 correspond to the edge of the DX8200A scanner as shown in the figure above. CONDITIONS Code = Interleaved 2/5 or Code 39 PCS = 0.
READING FEATURES 4 DX8200A-3X2X (0.30 mm/12 mils) The diagram shows an average reading area obtained considering different barcode types of variable quality. 0 z x Note: 0 -24 -60 -20 -50 -16 -40 -12 -30 -8 -20 -4 -10 0 0 4 10 8 20 12 30 16 40 20 50 24 60 28 (in) 70 -16 -40 -24 -32 -40 -48 -60 -80 -100 -120 -56 (in) -140 (cm) (cm) x = 0 and z = 0 correspond to the edge of the DX8200A scanner as shown in the figure above.
DX8200A 4 DX8200A-3X1X (0.38 mm/15 mils) The diagram shows an average reading area obtained considering different barcode types of variable quality. z x -28 -70 -24 -60 -20 -50 -16 -40 -12 -30 -8 -20 -4 -10 0 0 4 10 8 20 12 30 16 40 20 50 24 60 0 -16 0 -40 -24 -60 -32 -80 -40 -48 -56 -100 -120 -140 -64 (in) -160 (cm) 70 28 (cm) (in) Note: x = 0 and z = 0 correspond to the edge of the DX8200A scanner as shown in the figure above.
READING FEATURES 4 DX8200A-3X1X (0.50 mm/20 mils) The diagram shows an average reading area obtained considering different barcode types of variable quality. z x -28 -70 -24 -60 -20 -50 -16 -40 -12 -30 -8 -20 -4 -10 0 0 4 10 8 20 12 30 16 40 20 50 24 60 0 -20 -24 0 -50 -60 -32 -40 -48 -56 -64 -80 -100 -120 -140 -160 -72 -180 (in) (cm) 70 28 (in) (cm) Note: x = 0 and z = 0 correspond to the edge of the DX8200A scanner as shown in the figure above.
DX8200A 5 5 MAINTENANCE 5.1 CLEANING Clean the laser beam output windows periodically for correct operation of the scanner (see Figure A in chapter “General View”). Dust, dirt, etc. on the window may alter the reading performance. Repeat the operation frequently in particularly dirty environments. Use soft material and alcohol to clean the window and avoid any abrasive substances. Clean the window of the DX8200A when the scanner is turned off or at least when the laser beam is not active. WARNING 5.
MAINTENANCE 5.2.2 5 Scanner Replacement Procedure The ASR procedure requires replacing one scanner at a time. NOTE Slave 1. Power down the entire system. 2. Replace the Slave scanner with a new one (default settings). 3. Power up the system and wait for initialization. Master 1. Load the saved configuration from file (.ddc) to the new Master. 2. Power down the entire system. 3. Replace the Master scanner with the new one. 4. Power up the system and wait for initialization.
DX8200A 6 6 TROUBLESHOOTING NOTE Before contacting your local Datalogic office or Datalogic Partner or ARC, it is suggested to save the device configuration to a *.ddc file by means of the Genius™ software configuration program and check the device exact model and serial number. TROUBLESHOOTING GUIDE Problem Power On: the “Power On” LED is not lit. On Line Mode: the Master’s “Phase On” LED is not lit (when external trigger activates).
TROUBLESHOOTING 6 TROUBLESHOOTING GUIDE Problem On Line Mode and Serial On Line Mode: the reader does not respond correctly to the expected external signal end. Reading: it is not possible to read the target barcode (always returns No Read) Suggestion In the Genius™ software configuration program select the OPERATING MODES folder and check the “Reading Phase Timeout” parameterization. • • • • • • Communication: the device is not transmitting anything to • the host.
DX8200A 6 TROUBLESHOOTING GUIDE Problem Communication: the scanner “Network” LED is not lit. Suggestion • If the LED is OFF, check the connections between the DX8200A slaves and the SC6000 or DX8200A master. If the error persists, contact your Datalogic distributor. How do I obtain my units’ serial • The device serial number is printed on a label that is affixed above the connector panel of numbers? the reader. • The serial number is also displayed when connecting the device through the Genius™ program.
TECHNICAL FEATURES 7 7 TECHNICAL FEATURES ELECTRICAL FEATURES VAC models Supply voltage Power consumption Common Communication Interfaces VDC models 110 to 230 Vac 20 to 30 Vdc 30 VA typical 30 W typical 35 W Max. (including startup current) Main Baud Rate RS232 RS485 full-duplex RS485 half-duplex 20 mA C.L.
DX8200A 7 SOFTWARE FEATURES Readable Codes Code selection Headers and Terminators Operating modes Configuration modes Parameter storage ENVIRONMENTAL FEATURES Operating temperature Storage temperature Humidity Ambient light immunity Vibration resistance: EN 60068-2-6 2 hours on each axis Interleaved 2/5 Code 39 Standard Codabar Code 128 EAN 128 Code 93 (standard and full ASCII) EAN/UPC (including Add-on 2 and Add-on 5) Up to 10 codes during one reading phase Up to 128-byte headers and 128-byte terminator
SCANNER CONVERSION A A SCANNER VAC TO VDC CONVERSION (OPTIONAL) It is possible to convert the DX8200A VAC model into a VDC model by inserting an internal jumper. The following operation should be performed by qualified personnel only. CAUTION Before unscrewing the panel of the DX8200A, make sure the power supply cable is disconnected to avoid shock or harm to the operator. WARNING Follow the procedure below: 1. Unscrew the Display and Keypad panel screws to open the scanner. 2.
DX8200A A 3. Disconnect the internal Vdc power connector, referring to Figure 67. Figure 67 - Disconnecting the Vdc internal power supply connector 4. Connect the external Vdc jumper onto the power connector, referring to Figure 68. Figure 68 - Connecting the power supply jumper for external Vdc operation 5. Replace and tighten the Display and Keypad panel screws to close the scanner. You must supply Vdc power externally through the 17-pin connector.
GLOSSARY ACR™ 4 Each version of the base has the powerful code reconstruction technology (ACR™ 4). The new fourth generation ACR™ considerably increases the code reconstruction reading capability in the case of damaged or very tilted barcodes. Aperture Term used on the required CDRH warning labels to describe the laser exit window. Barcode A pattern of variable-width bars and spaces which represents numeric or alphanumeric data in machine-readable form.
LED (Light Emitting Diode) A low power electronic device that can serve as a visible or near infrared light source when voltage is applied continuously or in pulses. It is commonly used as an indicator light and uses less power than an incandescent light bulb but more than a Liquid Crystal Display (LCD). LEDs have extremely long lifetimes when properly operated. Multidrop Line A single communications circuit that interconnects many stations, each of which contains terminal devices. See RS485.
Trigger Signal A signal, typically provided by a photoelectric sensor or proximity switch, which informs the scanner of the presence of an object within its reading zone. UPC Acronym for Universal Product Code. The standard barcode type for retail food packaging in the United States. Visible Laser Diode A light source used in scanners to illuminate the barcode symbol. Generates visible red light at wavelengths between 630 and 680 nm.
INDEX A Accessories; 4 ACR™ 4; 54 C Cleaning; 68 Compliance; vi Electrical Safety; vi Laser Safety; vi Power Supply; vii WEEE Compliance; viii Connectors 26-pin connector; 9 DeviceNet; 23 Ethernet; 21 Profibus; 24 D DeviceNet; 23 E Electrical Connections; 7 G Genius™ Advanced Configuration; 49 Installation; 41 Wizard for Quick Reader Setup; 41 Glossary; 77 Guide to Installation; xii I Inputs; 13 Installation; 5 Mounting the Scanner; 6 Interfaces Auxiliary; 12 Ethernet; 22 Lonworks; 19 Main RS232; 10 Main RS
DATALOGIC S.p.A.