Installation manual
CBX ELECTRICAL CONNECTIONS 
43 
4 
4.3  ID-NET™ INTERFACE 
CBX100/500 
Function 
Shield 
Network Cable Shield 
ID+ 
ID-NET™ network + 
ID- 
ID-NET™ network - 
REF 
Network Reference 
4.3.1  ID-NET™ Cables 
The following instructions are referred to Figure 46, Figure 47 and Figure 48. 
  The general cable type specifications are: CAT5 twisted pair + additional CAT5 twisted 
pair, shielded cable AWG 24 (or AWG 22) stranded flexible. 
We recommend using DeviceNet cables (drop  or  trunk type) to  the  following reference 
standards: 
AN50325 – IEC 62026 
UL STYLE 2502 80°C 30V 
  Cable Shield MUST be connected to earth ground ONLY at the Master. 
  NEVER use ID-NET™ cable shield as common reference. 
  The ID-NET™ max cable length depends on the baudrate used, (see the Baudrate Table 
below). 
  For Common Power Connections use only 2 wires (ID+ and ID-). 
-  DC Voltage Power cable (Vdc – GND) should be handled as a signal cable (i.e. do not 
put it together with AC cable): 
-  Wire dimensioning must be checked in order to avoid voltage drops greater than 0.8 
Volts. 
-  Cable should lie down as near as possible to the ID-NET™ cable (avoiding wide loops 
between them). 
  Scanner's chassis may be connected to earth. 
  Network inside the same building. 
Baudrate Table 
Baud Rate 
125 kbps 
250 kbps 
500 kbps 
1Mbps 
Cable Length 
1200 m 
900 m 
700 m 
* 
* Application dependent, contact your Datalogic Automation representative for details. 
NOTE 
The  default  ID-NET™  baudrate  is  500  kbps.  Lower  ID-NET™  baudrates 
allow  longer  cable  lengths.  The  baudrate  is  software  configurable  by 
authorized Datalogic Automation personnel only. 