Command Server Timeout Profile
A command server timeout has been added while fixing the communication issues over TCPIP on poor network
connection. The default value on the Command _Server SESSION_TIMEOUT is zero, which will never disconnect the
connection. Any value can be set in seconds and command server session will end after inactivity for the specific period.
Values marked time in the table are specified in a similar way to schedule time intervals that is, an integer followed by a
unit letter (
D, H, M, S or T for days, hours, minutes, seconds and milliseconds respectively). Values marked cron-spec
are a "cron" time/date specifier, as described in Trigger at Date/Time (P52).
In the default column, (*) indicates that a suitable default value will be set automatically, if possible, based on the mobile
carrier that issued the SIM.
Examples
To set the DT80's IP address for the Ethernet port:
PROFILE ETHERNET IP_ADDRESS=192.168.1.225
To set the default date format to North American style:
PROFILE PARAMETERS P31=2
Note Special characters may be inserted into profile values using ^x or \nnn notation, as described in ASCII-Decimal Table (P389).
This means that if the profile value requires an actual
\ character then it must be entered twice, e.g.
PROFILE FUNCTION F1_COMMAND="DIR B:\\JOBS
Remember also that if DeTransfer is used to send the above line then the backslashes must be doubled again, i.e.
PROFILE FUNCTION F1_COMMAND="DIR B:\\\\JOBS
Setting the System Time
The DT80’s real-time clock/calendar is based on a 24-hour clock that has a resolution of approximately 0.1ms. This is
used to timestamp all logged data.
Time and date are maintained when the logger is switched off or reset. If the logger is switched off and the internal
Memory-Backup battery (see Internal Memory-Backup Battery (P291)) is removed or discharged, then the date and time
will be reset to 1989/01/01 00:00:00
D and T Channel Types
The DT80's time and date can be set using the T and D internal channel types (Time (P37)), e.g.:
T=13:05
Time 13:05:00.000
D=1/4/2006
Date 01/04/2006
The time and date must be specified in the current
P39 and P31 formats. The time can also be set to a CV value, where
the CV value is the number of seconds since midnight. Similarly for the date, except the value is now the number of
seconds since the base date (1/1/1989).
For example, to set the system time forward one hour you could use:
T(=1CV) 1CV(W)=1CV+3600 T=1CV
Time 15:59:23.460
Time 16:59:23.461
Note: only a single CV can be placed after the "=". Expressions are not supported.
DT Command
Alternatively, the DT command can be used to set both date and time. In this case the date/time is specified either in
dataTaker ISO format or ISO8601 format and enclosed in square brackets, e.g.:
DT=[2006/04/01,13:05:00] or
DT=[2006-04-01T13:05:00]
Time Zone
Depending on the application, you may choose to set the DT80's time to either:
local time. In this case you may need to alter the time periodically to adjust for daylight saving time, if applicable
local standard time. The logger is still set to the local time zone, but no correction is made for daylight saving
time
UTC (GMT) time. This may be appropriate if there are a number of DT80s (connected to the host computer via
a wide area TCP/IP network, for example) which are in different time zones
The DT80 and the dataTaker host software currently do not provide any specific support for data collected in disparate
time zones it is therefore up to the user to manage this.