Specifications

1
LP/NATURAL CONVERSION KIT INSTRUCTIONS
CT-365 SEALED BURNER COOKTOPS
CKL-CT365 Natural to LP
CKN-CT365 LP to Natural
Before you begin, read these instructions completely and carefully.
PARTS INCLUDED
Main Burner Orifice (5)
Simmer Burner Orifice (5)
Valve Bypass Jet (5)
Conversion Sticker (1)
Valve Stem C-Clip (5)
TOOLS NEEDED
1/8" Flat-blade Screwdriver
Adjustable Wrench
7mm Nut Driver
4mm Nut Driver (included)
Phillips Screwdriver
Ratchet with 1-1/16" Hex Deep Socket
25/32" Socket
Manometer
CAUTION:
Before proceeding with the conversion, shut-off gas supply to the appliance prior
to disconnecting the electrical power.
WARNING
This conversion kit must be installed by a qualified service agency in accordance with the
manufacturers instructions. All applicable codes and requirements of the authority
having jurisdiction must be followed. If the information in these instructions is not
followed exactly, fire, explosion or production of carbon monoxide may result, causing
property damage, personal injury or loss of life. The qualified service agency is
responsible for the proper installation of this kit. The installation is not proper and
complete until the operation of the converted appliance is checked as specified in the
manufacturers instructions supplied with the kit.
STEP 1
GAS SUPPLY
Measure the incoming gas pressure to the regulator.
With the installation of this conversion kit, the cooktop should operate on
LP gas at 10" of water column pressure and on natural gas at 4" of water
column pressure.
The pressure regulator must be connected in series with the
manifold of the cooktop and must remain in series with the supply
line.
When checking the regulator, the inlet pressure must be at least 1"
greater than the regulator output setting.
– If the regulator is set for 10" of water column pressure, the
inlet pressure must be at least 11".
For proper operation, the maximum inlet pressure to the regulator must
be no more than 14" of water column pressure for LP gas and 9" water
column pressure for natural gas.
Regulator
Solid Piping
or Flexible
Connector
Shut-Off
Valve
Pipe Stub
Connection: 1/2" N.P.T. -
minimum 5/8" dia. metal flex line.