Comparison Chart
LOCATION
Do not locate this unit or any electrical supply line directly over the heater. Electrical short or fire may occur
due to overheating. Follow the diagram below for appropriate zones for the installation of this unit (Fig. 08).
WARNING
The unit must be mounted outside the shaded areas shown in the diagram below (Fig. 08). The
remote control box must be installed in a location such that it is accessible for servicing.
30° max.
30° tip mount
infrared
pattern
horizontal mount
flue heat 48”
flue
heat 24”
FRONT VIEW SIDE VIEW SIDE VIEW
flue
heat 24”
Fig. 08 Infrared Pattern
BATTERY REPLACEMENT
1. Use 12-volt alkaline battery (type 23AE, see Fig. 04).
2. Open the battery compartment cover, and replace the old battery with a new one.
NOTE: DO NOT dispose of battery in fire. Battery may explode or leak.
TROUBLESHOOTING:
Heater does not come on.
1. Circuit breaker has tripped, power switch is in “OFF” position, or fuse is blown. Check circuit breaker,
power switch, or check and replace fuse if necessary.
2. Signals from remote control are being blocked, or remote is out of range. Check for metal objects
that could block the signal or reposition the remote control.
3. Weak battery in the remote control. Check/replace battery.
4. See troubleshooting guide the came with your heater.
Heater does not turn off.
1. Pushing remote control button too fast.
2. Same as 2~3 above.