6 Technical specifications
6.1 Technical specifications
6.1.1. Electricity supply
230 V AC (+/- 10%) - 50 Hz
6.1.2. Heat pump
Conditions of use:
4 Limit operating temperatures in Hot mode:
- Water: +18 °C / +55 °C
- Outside air:
-15 °C / +35 °C (AWHP 6 MR, 8 MR)
-20 °C / +35 °C (AWHP 11-27)
4 Limit operating temperatures in Cooling mode:
- Water: +7 °C / +25 °C
- Outside air: +15 °C / +40 °C (At less than 18°C, it is necessary
to use the HK24 insulation kit option)
4 Maximum operating pressure: 3 bar
AWHP
6 MR 8 MR 11 MR 11 TR 14 MR 14 TR 16 MR 16 TR 22 TR 27 TR
Calorific output -
A7/W35
(1)
kW 6.0 8.5 10.9 10.9 13.7 13.7 15.7 15.7 19.4 24.4
COP hot - A7/
W35
(1)
4.00 4.10 4.23 4.23 4.03 4.03 3.90 3.90 3.94 3.90
Absorbed
electrical power -
A7/W35
(1)
kWe 1.5 2.1 2.6 2.6 3.4 3.4 4.03 4.03 4.9 6.3
Nominal
amperage - A7/
W35
(1)
A 6.8 9.2 11.2 6.7 14.8 8.8 17.6 10.1 12.3 15.6
Calorific output -
A2/W35
(2)
kW 4.4 5.9 7.6 7.6 10.3 10.3 10.4 10.4 11.62 14.7
COP hot - A2/
W35
(2)
3.12 3.12 3.10 3.10 3.10 3.10 3.10 3.10 3.01 3.10
Absorbed
electrical power -
A2/W35
(2)
kWe 1.41 1.89 2.45 2.45 3.32 3.32 3.35 3.35 3.86 4.74
(1) Hot mode: Outside air temperature +7 °C, Water temperature at the outlet +35 °C. Performances in line with EN 14511-2.
(2) Hot mode: Outside air temperature +2 °C, Water temperature at the outlet +35 °C. Performances in line with EN 14511-2.
(3) Cooling mode: Outside air temperature +35 °C, Water temperature at the outlet +18 °C. Performances in line with EN 14511-2
(4) 5 m from the appliance, free field.
(5) Test conducted in accordance with the standard NF EN 12102
6. Technical specifications AWHP MIT-IN iSystem
29
09/01/13 - 300027618-001-02