Fryer User Manual
HIGH EFFICIENCY DECATHLON SERIES GAS FRYERS 
CHAPTER 1: SERVICE PROCEDURES 
1-6 
Interface Boards (cont.) 
FREQUENTLY USED TEST POINTS FOR HIGH EFFICIENCY DECATHLON (HD) FRYERS 
106-6669 INTERFACE BOARD 
Test Meter Setting Pins Test Results 
12VAC Power to Controller  50 VAC Scale  1 and 3 on J3  12-18 
12VDC Power to Right BL Relay  50 VDC Scale  4 on J2 and 5 on J2  12-18 
12VDC Power to Left BL Relay  50 VDC Scale  7 on J1 and 5 on J2  12-18 
24VAC Power to High-Limit  50 VAC Scale  6 on J2 and GROUND  22-28 
24VAC Power  50 VAC Scale  2 on J2 and GROUND  22-28 
24VAC Power To 24VAC Gas Valve  50 VAC Scale  7 on J2 and GROUND  22-28 
Probe Resistance*  R x 1000 Ohms  10 and 11 on J2  ** 
* Disconnect 15-pin harness from controller before testing probe circuit. 
** See Probe Resistance Chart at the end of this chapter. 
HIGH EFFICIENCY DECATHLON (HD) FRYER 
LED DIAGNOSTIC LIGHTS 
(106-6669 INTERFACE BOARD) 
CMP 
Indicates power from 12V transformer. 
24V 
Indicates power from 24V transformer. 
HI 
Indicates output (closed) from latch relay (K4). 
HT 
Indicates output from heat relay (K3). 
AL 
Indicates output (open) from latch relay (K4). 
The board contains four relays. K3 is the heat relay and K4 is the latch relay. K1 and K2 are only 
used in "dual" or "split" pot applications. 
NOTE: On factory-original units not equipped with basket lifts and on service interface boards, the 
board will have no basket lift relays installed. 