Operating instructions
Dedicated Micros ©2010
85
SD Advanced
Alarm Input
This menu allows conguration of the alarm settings, refer to ‘Installing the Unit’ for hardware 
installation guidance.
Number  This identies which input is being congured. The unit supports 
19 on-board alarms.
Ena  Each input must be enabled to function. If the input is not enabled 
and an alarm is received, the unit will not acknowledge the alarm. 
Module  The alarm contacts are connected via modules. Select the module 
that the contact to be congured is in. 
Contact  Select the Contact within the module to congure.
N_O (Normally Open Contact)  N_O indicates the non-alarm state of the input. Tick the N_O 
checkbox to set the corresponding input to Normally Open. The 
alarm will then trigger when the input is closed (shorted). If left as 
Normally Closed (the default setting), the alarm will trigger when 
the input is opened.
Note: If EOL alarms are to be used, this option should not be selected i.e. leave set as 
Normally Closed.
EOL  The End Of Line (EOL) option enables the inputs to detect any 
changes in the electronic input resistance. A change outside the 
expected values will result in a Tamper Alarm (short circuit or open 
circuit) being detected and the system switching to alarm mode.