Technical data

59
15/02/2011 - 300014279-001-J DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus
12. Installer settings
12.2 Settings relating to a heating circuit (continued)
* The line or title is only displayed for the options, circuits or
sensors actually connected.
At the end of the intervention, the data is stored after 2 minutes
or by closing the flap.
Press Display Parameter set Factory setting
Adjustment
range
Customer
setting
J
then
I
#FITTER PARAM. Setting parameters specific to the installation
using keys
or
.
CT.TEL: OPEN Telephone input activates if the contact is open
CLOSE
OPEN
CLOSE
CLOSE Telephone activates if the contact is closed.
I.TEL: ANTIFR Start anti-freeze in boiler command
ANTIFR
ANTIFR
DHW+HEAT
HEAT
DHW
THERM A
SWIM.
DHW+HEAT Hot water storage tank affected to heating and
domestic hot water.
HEAT Storage tank for heating.
DHW Storage tank for domestic hot water.
THERM A Connection of a room thermostat to circuit A.
SWIM. Used for the remote control of pool reheating
shutdown
.
NIGHT DEC. The lower temperature is maintained
DEC.
DEC. or STOP
STOP The boiler is stopped
IN 0-10V
Activating the control at 0-10 V
.
OFF OFF/ON
VMIN/OFF 0-10V* Voltage corresponding to the instruction set
minimum
.
0.5 V 0 to 10 V
VMAX 0-10V* Voltage corresponding to the instruction set
maximum
.
9.5 V 0 to 10 V
CONS.MIN 0-10V* Instruction minimum set temperature. 20 °C 10 to 70 °C
CONS.MAX 0-10V* Maximum set temperature. 80 °C 10 to 100 °C