Technical data
41
08/06/06 - 300008460-001-B MCR 24, 24/28 MI, 30/35 MI, 34/39 MI
2.5 Modify parameters
- Press the Ä key until the symbol is displayed.
- Select the fitter menu using the l key. The symbol COdE
appears.
- Enter the fitter code 0012 using the - or + key.
- To confirm, press the l key. The symbol P:1 appears.
- Press the l key a second time. The symbol 75°C appears
(Factory setting).
- Lower the value to 60°C using the - key.
- To confirm, press the l key
- To confirm, press the l key. The symbol P:1 appears.
- If necessary, set other parameters by selecting them using the - or
+ keys.
- Press key 2 time to return to the current operating mode.
If no selections are made in the various modes for 10 minutes,
the boiler resumes the settings prior to manipulation.
2.6 Setting the maximum output (Hi): Heating
Parameter P17 (maximum fan speed) is used to modify maximum
central heating output.
Fan speed/boiler output ratio
• MCR 24
• MCR 24/28 MI
• MCR 30/35 MI, MCR 34/39 MI
X: Boiler power (kW)
Y: Fan rotation speed (rpm)