Technical data

44
MCR 24, 24/28 MI, 30/35 MI, 34/39 MI 08/06/06-300008460-001-B
Adapting to another gas
For Belgium: Only SERV’élite is authorised to carry out the
conversion of this appliance.
MCR boilers are preset in the factory for natural gas H.
The actions described below must be carried out by a
qualified technician.
For Belgium: The boiler installation and gas connection
must be carried out by a qualified professional in
compliance with the NBN D 51.003, NBN D 30.003, NBN B
61.001, NBN B 61.002 and NBN D 51.006 standards.
1 Switching from Natural Gas to Propane
The conversion from Natural Gas to Propane requires only the
adjustment of the burner and the fan speed.
2 Setting the control unit parameters
For conversion to propane
To obtain the gas valve setting used to start up with propane, use the
following instructions:
- GN (G20) to G31: Turn the high speed adjustment screw 2
rotations clockwise
or
- Turn high speed screw clockwise until it is closed. Turn high speed
adjustment screw 3.5 - 4 rotations counter clock wise.
After this setting, the boiler will not have an optimum setting for
propane.
For the precise setting, use a CO
2
measuring device and apply the
settings procedures:
Z
See "Modify parameters" and "Setting the gas/air ratio - Full
load + Part load"
Parameter Nominal fan
speed
(rpm)
MCR 24
Nominal fan speed
(rpm)
MCR 24/28MI
Nominal fan
speed
(rpm)
MCR 30/35MI
Nominal fan
speed
(rpm)
MCR 34/39MI
CO
2
%
Natural gas H
(Factory setting :
Gn by default)
Nominal power
h3
P17 3700 3700 4100 4700 8.8±0.3
Minimum output
L3
P19 1300 1300 1300 1300 8.8±0.3
Maximum DHW
speed
H3
P18 4600 5500 6300 6700 8.8±0.3
Propane (Factory
setting : Pr)
Nominal power
h3
P17 3500 3500 3900 4500 10.5±0.3
Minimum output
L3
P19 2000 2000 2000 2000 10.5±0.3
Maximum DHW
speed
H3
P18 4400 5200 6000 6400 10.5±0.3