Datasheet

© DEHN + SÖHNE GmbH + Co. KG · Hans-Dehn-Str. 1 · Postfach 1640 · D-92306 Neumarkt · Tel. +499181 906-0 · www.dehn.de
3,
t
e
s
t
e
d
: Tested +: New (: Discontinued Model
Product Data Sheet: DEHNguard® modular
DG M TT 275 FM (952 315)
Prewired complete unit consisting of a base part and plug-in protection modules
High discharge capacity due to heavy-duty zinc oxide varistors / spark gaps
High reliability due to "Thermo Dynamic Control" SPD monitoring device
Figure without obligation
Basic circuit diagram DG M TT 275 FM Dimension drawing DG M TT 275 FM
Modular surge arrester for use in TT and TN-S systems (3+1 configuration); with floating remote signalling contact.
Type
DG M TT 275 FM
Part No.
952 315
SPD according to EN 61643-11 / IEC 61643-11
type 2 / class II
Energy coordination with terminal equipment (≤ 10 m)
type 2 + type 3
Nominal voltage (a.c.) (U
N
)
230 / 400 V (50 / 60 Hz)
Max. continuous operating voltage (a.c.) [L-N] (U
C
)
275 V (50 / 60 Hz)
Max. continuous operating voltage (a.c.) [N-PE] (U
C
)
255 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (I
n
)
20kA
Max. discharge current (8/20 µs) (I
max
)
40kA
Lightning impulse current (10/350 µs) [N-PE] (I
imp
)
12kA
Voltage protection level [L-N]/[N-PE] (U
P
)
≤ 1.5 / ≤ 1.5kV
Voltage protection level [L-N] / [N-PE] at 5 kA (U
P
)
≤ 1 / ≤ 1.5kV
Follow current extinguishing capability [N-PE] (I
fi
)
100A
rms
Response time [L-N] (t
A
)
≤ 25ns
Response time [N-PE] (t
A
)
≤ 100ns
Max. mains-side overcurrent protection
125A gG
Short-circuit withstand capability for max. mains-side overcurrent
protection (I
SCCR
)
50kA
rms
Temporary overvoltage (TOV) [L-N] (U
T
) – Characteristic
335 V / 5 sec. – withstand
Temporary overvoltage (TOV) [L-N] (U
T
) – Characteristic
440 V / 120 min. – safe failure
Temporary overvoltage (TOV) [N-PE] (U
T
) – Characteristic
1200 V / 200 ms – withstand
Operating temperature range (T
U
)
-40 °C ... +80 °C
Operating state / fault indication
green / red
Number of ports
1
Cross-sectional area (min.)
1.5 mm
2
solid / flexible
Cross-sectional area (max.)
35 mm
2
stranded / 25 mm
2
flexible
For mounting on
35 mm DIN rails acc. to EN 60715
Enclosure material
thermoplastic, red, UL 94 V-0
Place of installation
indoor installation
Degree of protection
IP 20
Capacity
4module(s), DIN 43880
Approvals
KEMA, VDE, UL
Type of remote signalling contact
changeover contact
Switching capacity (a.c.)
250 V / 0.5 A
Switching capacity (d.c.)
250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Cross-sectional area for remote signalling terminals
max. 1.5 mm
2
solid / flexible
Extended technical data:
---------------------------------
Voltage protection level [L-PE] (U
P
)
1.5kV
Weight
415g
Customs tariff number (Comb. Nomenclature EU)
85363030
GTIN
4013364108486
PU
1pc(s)
We reserve the right to introduce changes in performance, configuration and technology, dimensions, weights and materials in the course of technical progress. The figures are shown without obligation.

Summary of content (1 pages)