Datasheet

Features:
Single Output with Universal input 100~240 VAC
Installable on DIN rail TS35 / 7.5 or 15
Overload & over voltage protection
Short circuit shutdown & auto recovery
100% burn-in tested
1 year warranty
Specification:
MODEL DRP-072D-05FT DRP-072D-12FT DRP-072D-24FT DRP-072D-48FT
Voltage (VDC) 5.1V 12V 24V 48V
min. Load 0A 0A 0A 0A
Rated Load 14.4A 6A 3A 1.5A
max. Load 14.4A 6A 3A 1.5A
Tolerance ± 2% ± 1% ± 1% ± 1%
Ripple & Noise (max) 70mV 100mV 150mV 250mV
Efficiency (min) 73% 76% 78% 78%
Max. Output Power 72W
Output Voltage adjustment range ± 10%
Voltage Universal input 100~240 VAC or 127~380VDC
Frequency 47 ~ 440 Hz
Current 2A max.
INPUT
Inrush Current <40A@220VAC / <20A@110VAC @ 25°C
Overload auto power limiting
Over Voltage 5.8 ~ 7VDC 15 ~ 18VDC 27.6 ~ 31VDC 52 ~ 58VDC
Over Temp. -
PROTECTION
Short Circuit Shutdown, auto recovery after fault has been removed
Holdup time > 16ms @ 110VAC
Cooling Free air convection
Vibration 2G, 10~500Hz, 3 axes
OTHERS
Temperature Operating: -15 ~ 50°C / Storage: -20 ~ 85°C
Environment
Humidity Operating: 5% ~ 95% RH (non condensing)
M.T.B.F. > 280K hours (according to MIL-HDBK-217F at 25°C environment)
SAFETY Approved:
UL 60950 / CSA 60950 / CE
EMI EN55022 Class B / EN 61000-3-2, 3
EMC
EMS EN55024 / EN61000-4-2,3,4,5,6,8,11
WEIGHT N.W. : 430g
DRP-072D DIN Rail 72W
Country of Origin : China
Operating Temperature : -15 ~ 50° C
Dimension : 100 x 49 x 83 mm
Approvals / Marks : UL, c-UL, CSA, CE
info / drawing : www.dehner.net/drp-072d Specifications subject to change without notice