User's Manual

GE Contactless Medium Read-Range Reader Model 260 13
Micro Selection
Micro/5 for 2RP and 8RP installation instructions: refer to the Micro/5
Installation Guide.
IMPORTANT: DO NOT use the Model 260 Reader with a Micro/5 2SRP reader
processor.
Micro/PX-2000 and Micro/PXN-2000 controllers: refer to the Micro/
PX-2000 and Micro/PXN-2000 Installation Guide.
Micro/Reader-Junction Box: refer to the point-to-point wiring
diagrams in this manual.
Reader-to-Micro Wiring Distance
Table 1: Model 260 Current and Cable Distance
Cable Distance
Supply
Voltage
12 VDC 13.6 VDC 24 VDC
Current 18 AWG 22 AWG 18 AWG 22 AWG 18 AWG 22 AWG
Distance
230 mA
@12 VDC
928 ft.
(283 m)
390 ft.
(119 m)
1,423 ft.
(434 m)
597 ft.
(182 m)
4,649 ft.
(1,417 m)
1,949 ft.
(594 m)