Versatec 500 WSHP 7-30 Ton Installation Manual Formerly Versatec XL Commercial Water Source/Geothermal Heat Pump • R-410A Refrigerant • 7-30 Tons Installation Information Water Piping Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance IM2770AU 03/22
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Table of Contents Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Electrical Availability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Model Nomenclature 1-2 3 4-6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22-23 24 UD V 096 T L 3 N 5 0 D A N A N 0 A 1 N SS * Model Type Versatec XL Series Vintage *– Factory Use Cabinet Configuration V – Vertical (084-360) H – Horizontal (084-180) T – Vertical Take-a-Part (240-360) Non-Standard Options SS – Standard Economizer Option N – None W – Waterside Economizer² Unit Capacity 084, 096, 120, 15
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL General Installation Information Unit Location Safety Considerations Locate the unit in an indoor area that allows for easy removal of the filter and access panels. Location should have enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connection(s).
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Dimensional Data LEFT RETURN SHOWN "N" 1.0 "M" "J" "B" "L" "H" TOP DISCHARGE FIELD REMOVABLE BLOWER PANEL INSERT 1.00 "G" 2.1 2.3 "M" "L" "N" BLOWER ACCESS PANEL "K" BLOWER ACCESS PANEL "P" BOTH SIDES "C" SIDE DISCHARGE FIELD REMOVABLE BLOWER PANEL INSERT DRAIN CONNECTION 1.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Dimensional Data cont. 1.4 LEFT RETURN SHOWN "H" "F" END DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES DRAIN CONNECTION SIDE DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES "J" "N" 1.7 2.1 "J" 1.7 1.0 DUCT FLANGE "K" "G" "L" "H" "K" AIR COIL "M" "V" BLOWER ACCESS PANEL "B" "A" "U" 40.00 "P" "P" "R" "R" "T" 1 5/8" UNISTRUT 42" CUT LENGTH 3 REQUIRED NOT SUPPLIED BY WFI 1.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Dimensional Data cont. 240-360 RIGHT RETURN SHOWN POWER SUPPLY LEFT RETURN 16.88 3.40 8.10 1.50 16.08 48.08 71.90 POWER SUPPLY RIGHT RETURN 20.00 8.10 REF 3.40 7.00 34.00 TOP DISCHARGE FIELD REMOVABLE BLOWER PANEL INSERT 36.90 1.00 88.00 1.70 46.00 CONTROL BOX ACCESS DOOR 80.00 1.80 7/8" O.D. DRAIN CONNECTION WATER OUT 2" FPT WATER IN 2" FPT 31.30 7.00 8.00 6.60 20.80 1.90 (3) 32.62 8 22.75 REF 32.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Dimensional Data cont. UDV084-180 TOP FLOW ECONOMIZER OPTION LR "N" 1.0 "J" "M" "H" "B" "L" 4.5 TOP DISCHARGE FIELD REMOVABLE BLOWER PANEL INSERT "G" 1.00 "A" 2.1 "L" 2.3 "M" BLOWER ACCESS PANEL "N" TOP DISCHARGE FIELD REMOVABLE BLOWER PANEL INSERT "K" "P" BOTH SIDES "C" DRAIN CONNECTION BLOWER ACCESS PANEL 1.8 CONTROL BOX ACCESS DOOR "E" "R" BOTH SIDES "F" "D" 4.1 34.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Dimensional Data cont. UDV084-180 TOP FLOW ECONOMIZER OPTION RR 1.0 "N" 2.2 "B" "J" "M" "L" TOP DISCHARGE FIELD REMOVABLE BLOWER PANEL INSERT "M" "L" 2.3 1.0 8.1 "G" 2.1 "A" BLOWER ACCESS PANEL "N" "K" TOP DISCHARGE FIELD REMOVABLE BLOWER PANEL INSERT BLOWER ACCESS PANEL "C" "P" BOTH SIDES DRAIN CONNECTION 1.8 CONTROL BOX ACCESS DOOR "R" BOTH SIDES "D" 34.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Dimensional Data cont. 2.1 LEFT RETURN SHOWN 1.4 "H" "F" END DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES SIDE DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES "J" DRAIN CONNECTIONS "J" "N" 2.1 AIR COIL 1.7 1.0 DUCT FLANGE "K" 1.7 "G" "M" "V" BLOWER ACCESS PANEL "B" "A" 50.00 (2) "U" 22.8 20.4 40.00 "P" "P" "R" "R" "T" 1.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Dimensional Data cont. "H" 2.1 1.5 RIGHT RETURN SHOWN END DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES "J" SIDE DISCHARGE FIELD REMOVABLE BRACKETS AND DUCT FLANGES "J" 1.7 1.0 DUCT FLANGE "K" 1.7 2.1 "N" "H" "K" "G" "M" "V" AIR COIL BLOWER ACCESS PANEL "B" 50.00 (2) "A" "U" 22.9 20.3 40.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Dimensional Data cont. 16.88 3.40 1.50 8.10 16.08 48.08 20.00 UDV240-360 RIGHT RETURN SHOWN POWER SUPPLY LEFT RETURN 71.90 POWER SUPPLY RIGHT RETURN 8.10 REF 3.40 7.00 34.00 TOP DISCHARGE FIELD REMOVABLE BLOWER PANEL INSERT 44.88 1.00 88.00 1.70 46.00 CONTROL BOX ACCESS DOOR 80.00 WATER OUT 2" FPT WATER IN 2" FPT 31.30 7.00 1.80 8.00 6.60 20.80 1.90 (3) 32.62 13 22.75 REF 32.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Installation Notes piping system. This hose is typically stainless steel braid and includes a swivel fitting on one end for easy removal and is flexible to help isolate the unit for quieter operation. Isolation valves for servicing, y-strainers for filtering and memory-stop flow valve or a balancing valve can be provided for consistent water flow through the unit.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Installation Notes cont. Installing Horizontal Units channel as shown in the Horizontal Dimensional Data. The unit should be pitched approximately 1/4 in. toward the drain in both directions to facilitate the removal of condensate. Remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket prior to setting the unit in place. Horizontal units are available with side or end discharge.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Installation Notes cont. Ductwork • Ensure return air grilles will not allow line of site noise to transfer to adjacent space. Use a sound barrier or some other material to isolate the grille from the unit. A supply grille, boot and short piece of flex duct pointed away from the unit can greatly attenuate equipment noise. • Use a canvas isolation duct connector at the supply and return duct connection of the unit.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Duct System An air outlet collar is provided on vertical top flow units and all horizontal units to facilitate a duct connection. A flexible connector is recommended for discharge and return air duct connections on metal duct systems. Uninsulated duct should be insulated with a minimum of 1-inch duct insulation.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Condensate Drain On vertical units, the internal condensate drain assembly consists of a drain tube which is connected to the drain pan, a 3/4 in. PVC female adapter and a flexible connecting hose. The female adapter may exit either the front or the side of the cabinet. The adapter should be glued to the field-installed PVC condensate piping.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Water Quality with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing. Failure to adhere to the guidelines in the water quality table could result in loss of warranty. In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL System Cleaning and Flushing Refill the system with clean water. Test the system water for acidity and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The specified percentage of antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVAC systems only. Environol™ brand antifreeze is recommended.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Open Loop Ground Water Systems Typical open loop piping is shown below. Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Electrical Connections General 208 Volt Operation Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable. All 208/230 volt units are factory wired for 230 volt operation. For 208 volt operation, the red and blue transformer wires must be switched on terminal strip PS.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Electrical Data Electrical Table 7-30 Ton Plenum Fan Compressor (each) Two Compressors & Two Plenum Fans Two Compressors & Plenum Fan Dual Capacity Compressor Model 084 096 120 150 180 240 300 360 HACR circuit breaker Rated Voltage Voltage Min/Max MCC RLA 208-230/60/3 460/60/3 575/60/3 208-230/60/3 460/60/3 575/60/3 208-230/60/3 460/60/3 575/60/3 208-230/60/3 460/60/3 575/60/3 208-230/60/3 460/60/3 575/60/3 208-230/60/3 460/
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Blower Performance Data Integrated EC Backward Curved Plenum Fan Performance Model 084 Fan Fan Speed 1 2 3 4 5 6 7 8 9 10 11 12 RPM 900 1100 1300 1400 1600 1700 1800 1900 2000 2100 2200 2300 0.0 1395 1725 2055 2220 2555 2715 2810 2970 3145 3320 3460 3625 0.1 1315 1640 1985 2165 2505 2660 2785 2910 3105 3300 3415 3575 0.2 1215 1570 1925 2100 2435 2610 2705 2865 3075 3285 3380 3505 0.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Blower Performance Data cont. Model 150 Fan Fan Speed RPM Airflow [cfm] at External Static Pressure [in. wg.] 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1 900 2780 2665 2545 2400 2230 2055 1880 1650 2 1000 3095 2990 2885 2780 2675 2515 2345 2175 3 1100 4 1200 3750 3660 3565 3470 3370 3275 3165 3055 2935 2805 2680 2530 2375 2195 1995 1.5 1.6 1.7 1.8 1.9 2.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Blower Performance Data cont. Model 240 Fan Fan Speed RPM 1 2 3 4 5 6 7 8 9 10 11 12 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 Airflow [cfm] at External Static Pressure [in. wg.] 0.7 0.8 0.9 1.0 1.1 1.2 1.3 0.0 0.1 0.2 0.3 0.4 0.5 0.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Blower Performance Data cont. Setting Blower Speed - Variable Speed ECM ECM Speed Setup - These screens allow the technician to select the G, low, high, and auxiliary heat blower speed for the ECM blower motor. Change the highlighted item using the ▲ and ▼ buttons. Press the ◙ button to select the speed.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics Single Compressor 208-230/60/3 Ultra Tech CS See N ote 6 FP2/ LP LAT RV RCP CC Blue Black (19) P9 CC F C R F FG CC CCG Blue (23) CC2 CC2 CC2 P5 HI LO G Blue (8) Black C R F1-3A F K6-Acc Relay Status LED3 G SW1 Aurora Base Control (ABC) Test Mode CFM C P13 Faul t LED1 R O/B G Y1 Red Black (10) K1-RV Relay Red T Black (9) PWM LO R C Gray T Blue (7) REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPS P4 K3
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Wiring Schematics cont.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Aurora Controls Aurora Controls The Aurora Control System is a complete commercial comfort system that can bring all aspects of the HVAC system into one cohesive module network. The Aurora System is available in two configurations: Aurora Base Control and Aurora Advanced and Aurora Premium Control both with optional Aurora UPC for DDC applications.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Aurora Controls cont. Aurora ‘Base’ Control Control Features Software ABC Standard Version 3.0 Single or Dual Capacity Compressors Either single or dual capacity compressors can be operated. Variable Speed ECM Blower Motor Option (If Applicable) A Variable Speed ECM blower motor can be driven directly using the onboard PWM output. Four blower speeds are available based upon the G, Y1, Y2, and W input signals to the board.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Aurora Controls cont. Field Selectable Options via Hardware DIP Switch (SW2) DIP Switch (SW1) – Test/Configuration Button (See SW1 SW2-1 FP1 Selection – Low water coil temperature limit setting for freeze detection. On = 30°F; Off = 15°F. SW2-2 FP2 Selection – On = 30°F; Off = N/A SW2-3 RV – O/B - thermostat type. Heat pump thermostats with “O” output in cooling or “B” output in Heating can be selected. On = O; Off = B.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Aurora Controls cont. removed, all of the emergency heat outputs will turn off, and the ECM blower will shift to “G” speed and PSC blower motor output will remain on. Field Selectable Options via Software (Selectable via the Aurora AID Tool) ECM Blower Speeds An ECM blower motor can be driven directly using the onboard PWM output. Four blower speeds are available, based upon the “G”, Y1 (low), Y2 (high), and Aux input signals to the board.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Aurora Controls cont. Single Compressor Cooling, 2nd Stage (Y1, Y2, 0) The compressor will be staged to full capacity 20 seconds after Y2 input was received. The ECM blower will shift to high speed 15 seconds after the Y2 input was received. Operation Description Power Up - The unit will not operate until all the inputs and safety controls are checked for normal conditions. The unit has a 5 to 80 second random start delay at power up.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Aurora Controls cont. Aurora ‘Base’ Control LED Displays Aurora Interface and Diagnostics (AID) Tool These three LEDs display the status, configuration, and fault codes for the control. These can also be read in plain English via the Aurora AID Tool. The Aurora Interface and Diagnostics (AID) Tool is a device that is a member of the Aurora network.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Aurora Controls cont. Aurora Advanced and Aurora Premium Controls Aurora Advanced And Aurora Premium Control Features The Aurora ‘Advanced’ Control system expands on the capability of the Aurora ‘Base’ Control (ABC) by adding the Aurora Expansion Board (AXB). All of the preceding features of the Aurora ‘Base’ Control are included. The following control description is of the additional features and capability of the Aurora advanced control.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Aurora Controls cont. Variable Speed Pump Performance Monitoring (Standard with Premium Controls) This input and output are provided to drive and monitor a variable speed pump. The VS pump output is a PWM signal to drive the variable speed pump. The minimum and maximum level are set using the AID Tool. 75% and 100% are the default settings respectively.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Aurora Controls cont. Aurora ‘Advanced’ Control LED Displays These three LEDs display the status, configuration, and fault codes for the control. These can also be read in plain English via the Aurora AID Tool.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Unit Startup Before Powering Unit, Check The Following: • • • • • • • • • • • • • • Power supply matches nameplate specifications. Power supply fuses, breakers and wires are sized correctly. Switch the Transformer to 208V if applicable. Low voltage wiring complete. Piping completed and water system cleaned and flushed. Air is purged from closed loop system. Isolation valves are open, water control valves or loop pumps wired.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Operating Limits Cooling (°F) (°C) Operating Limits Air Limits Min. Ambient Air 45 Rated Ambient Air 80 Max. Ambient Air 100 Min. Entering Air 50 Rated Entering Air db/wb 80.6/66.2 Max. Entering Air db/wb 110/83 Water Limits Min. Entering Water 30 Normal Entering Water 50-110 Max. Entering Water 120 Heating (°F) (°C) 7.2 26.7 37.8 10.0 27/19 43/28.3 45 70 85 40 68 80 7.2 21.1 29.4 4.4 20.0 26.7 -1.1 10-43.3 48.9 20 30-70 90 -6.7 -1.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Operating Parameters cont. Second Stage Operation Cooling -- No Hot Water Generation Entering Water Water Flow Temp °F gpm/ton Suction Pressure psig Discharge Pressure psig Superheat Subcooling Water Temp Rise Air Temp Drop °F DB °F 30 1.5 3.0 115 - 125 105 - 120 150 - 170 130 - 145 20 - 35 20 - 35 10 - 17 10 - 17 17 - 22 8 - 10 17 - 23 17 - 23 50 1.5 3.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Reference Calculations Heating Calculations: Cooling Calculations: HR gpm x 500 LWT = EWT - HE gpm x 500 LWT = EWT + LAT = EAT + HC cfm x 1.08 LAT(DB) = EAT(DB) - SC cfm x 1.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Refrigerant Circuit Guideline Head Pressure Suction Pressure Compressor Amp Draw Superheat Subcooling Air Temp. Differential Water Temp.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Compressor and Thermistor Resistance Compressor Resistance Chart 460/60/3 0.47-0.55 2.07-2.39 460/60/3 3.33-3.83 096 0.47-0.54 1.85-2.13 3.33-3.83 Dual Capacity 208-230/60/3 084 120 0.33-0.39 1.28-1.48 2.17-2.49 Two Compressor Model 150 0.68-0.78 2.09-2.41 4.01-4.61 2.57-2.95 180 0.47-0.54 1.66-1.92 240 0.33-0.39 1.28-1.48 2.17-2.49 300 0.26-0.30 0.47-0.54 1.76-2.02 360 0.2 0.83 1.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Troubleshooting Should a major problem develop, refer to the following information for possible causes and corrective steps. If compressor won’t run: 1. 2. 3. 4. 5. 6. 7. 8. 9. The fuse may be open or the circuit breaker is tripped. Check electrical circuits and motor windings for shorts or grounds. Investigate for possible overloading. Replace fuse or reset circuit breakers after fault is corrected. Supply voltage may be too low.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Startup and Troubleshooting Form Company Name: _________________________________ Technician Name: ________________________________ Model No: ______________________________________ Owner’s Name: __________________________________ Installation Address: ______________________________ Company Phone No: ______________________________ Date: __________________________________________ Serial No:_______________________________________ Open or Closed
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL DEALER: PHONE #: DATE: PROBLEM: MODEL #: Startup/Troubleshooting Form SERIAL #: COOLING CYCLE ANALYSIS PSI = SAT °F °F Unit Amp Draw: °F AIR COIL Loop: Open Closed Line Voltage: °F SUCTION COMPRESSOR COAX COAX EXPANSION VALVE LOAD REVERSING VALVE SOURCE DISCHARGE Hot Water Generator $F °F LIQUID LINE °F °F °F °F PSI PSI PSI PSI °F BRINE IN BRINE IN BRINE OUT SAT $F PSI = Superheat °F Subcooling BRINE OU
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Preventive Maintenance Water Coil Maintenance 1. Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to infiltrate the water line. Lines should always be airtight. 2. Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be placed in the discharge line to prevent loss of pressure during off cycles.
VERSATEC 500 7-30 TON INSTALLATION MANUAL - Formerly Versatec XL Revision Guide Pages: 3 Cover All Description: Date: By: Nomenclature Update 05 Mar 2022 JM Name Update 10 Jan 2022 JM Document Creation 15 July 2021 JM 68
Manufactured by WaterFurnace International, Inc. 9000 Conservation Way Fort Wayne, IN 46809 www.waterfurnace.com *IM2770AU* IM2770AU 03/22 Product: Type: Size: Document: Versatec 500 Water Source/Geothermal Heat Pump 7-30 Tons Installation Manual ©2022 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and reserves the right to change design and specifications without notice.